
C2: V/f control parameters
Code
Name
Setting range
Default
Min.
Attri.
C2.00 V/f curve mode
0: Linear
1: Square
2: User-defined
0
–
Stop
C2.01 V/f frequency 1
0.00...[C2.03] Hz
0.00
0.01
Stop
C2.02 V/f voltage 1
①
0.0...120.0 %
0.0
0.1
Stop
C2.03 V/f frequency 2
[C2.01]...[C2.05] Hz
0.00
0.01
Stop
C2.04 V/f voltage 2
①
0.0...120.0 %
0.0
0.1
Stop
C2.05 V/f frequency 3
[C2.03]...[E0.08] Hz
50.00
0.01
Stop
C2.06 V/f voltage 3
①
0.0...120.0 %
100.0
0.1
Stop
C2.07 Slip compensation factor
0…200 %
0
1
Run
C2.20 0 Hz output mode
0: No output
1: Standard
1
1
Stop
C2.21 Torque boost setting
0.0 %: Automatic boost
0.1...20.0 %: Manual boost
DOM
0.1
Run
C2.22 Automatic torque boost factor 0...320 %
50
1
Run
C2.23
Heavy load stabilization
setting
0: Inactive
1: Active
1
–
Run
C2.24
Light load oscillation damping
factor
0...5,000 %
0
1
Run
C2.25
Light load oscillation damping
filter factor
10...2,000 %
100
1
Run
C2.40 Current limitation mode
0: Always inactive
1: Inactive at constant speed
2: Active at constant speed
2
–
Stop
C2.42 Current limitation level
②
[C0.27]...250 %
150
1
Stop
C2.43 Current limitation proportional
gain
0.000...10.000
DOM
0.001
Stop
C2.44
Current limitation
integral time
0.001...10.000
DOM
0.001
Stop
①
: percentage of motor rated voltage [C1.06].
②
: percentage of frequency converter rated current.
Bosch Rexroth AG
Appendix
VFC 3210
234/253
DOK-RCON04-VFC3210****-IT01-EN-P