12.9.6 PID Deactivation by Digital Input
Fig. 12-39: PID deactivation by digital input
The PID control is deactivated in the following ways:
●
'PID reference channel' [E4.00] = '0: No PID control' or
●
[E1.00]...[E1.04] / [H8.00]...[H8.03] = '41: PID deactivation' and respective
multi-function digital input terminal is active.
12.9.7 PID Engineering Value Display
This function is used to display an engineering value which is convenient for the
application engineering with scaling the output value, follow the equations be-
low:
●
User-defined setting speed:
[d0.04] = [d0.02] x [E5.02]
●
User-defined actual speed:
[d0.05] = [d0.00] x [E5.02]
Code
Name
Setting range
Default
Min.
Attri.
E5.02 User-defined speed scaling factor
0.01...100.00
1.00
0.01
Run
d0.01 Actual speed
–
–
1 rpm Read
d0.03 Setting speed
–
–
1 rpm Read
d0.04 User-defined setting speed
–
–
0.1
Read
d0.05 User-defined output speed
–
–
0.1
Read
d0.70 PID reference engineering value
–
–
0.1
Read
d0.71 PID feedback engineering value
–
–
0.1
Read
[d0.70] = [E4.02] x [PID reference]
[d0.71] = [E4.02] x [PID feedback]