E1: Input terminal parameters
Code
Name
Setting range
Default
Min.
Attri.
E1.00 X1 input
0...51
35
–
Stop
E1.01 X2 input
36
–
Stop
E1.02 X3 input
0
–
Stop
E1.03 X4 input
0
–
Stop
E1.15 2-wire / 3-wire control mode
0...4
0
–
Stop
E1.16 Digital input Up / Down change rate
0.10...100.00 Hz/s
1.00
0.01
Run
E1.17 Digital input Up / Down initial frequen-
cy
0.00...[E0.09] Hz
0.00
0.01
Run
E1.35 AI1 input mode
0: 0...20 mA
1: 4...20 mA
2: 0...10 V
3: 0...5 V
4: 2…10 V
2
–
Run
E1.38 AI1 gain
0.00...10.00
1.00
0.01
Run
E1.60 Motor temperature sensor channel
0: Inactive
1: AI1 analog input
0
–
Stop
E1.61 Broken wire protection
0: Inactive
1: Warning
2: Error
0
–
Stop
E1.69 Analog input filter time
0.000...2.000 s
0.100
0.001
Run
E1.70 Input curve 1 minimum
0.0 %...[E1.72]
0.0
0.1
Run
E1.71 Input curve 1 minimum frequency
0.00...[E0.09] Hz
0.00
0.01
Run
E1.72 Input curve 1 maximum
[E1.70]...100.0 %
100.0
0.1
Run
E1.73 Input curve 1 maximum frequency
0.00...[E0.09] Hz
50.00
0.01
Run
Setting range of E1.00...E1.03:
0: Inactive
1: Multi-speed control input 1
2: Multi-speed control input 2
3: Multi-speed control input 3
10: Acceleration / deceleration time 1 activation
11: Acceleration / deceleration time 2 activation
12: Acceleration / deceleration time 3 activation
15: Freewheeling stop activation
16: Stop DC-braking activation
Bosch Rexroth AG
Appendix
VFC 3210
238/253