Menu mode: Operation and setting
73
ATICS-DIO_D00080_01_M_XXEN/04.2015
7.3.4.5
Settings menu 5: Digital Input
On this menu, you can adjust settings for the mode of operation and function of the digital inputs.
The digital inputs are galvanically isolated. They are designed for an input signal of AC/DC 24 V.
For each input, selection is possible when the input is set to: "24V" (high) or "0V" (low). In the "24V"
setting, the selected function (e.g. alarm message) is carried out when there are 24 volts there. In the
"0V" setting, the selected function is carried out when there are 0 volts there. It is for this reason that
you should always set unused digital inputs to "off".
Select the digital input:
1. Use the arrow button "
" to set the digital input. Press "
↵
".
2. Use the arrow buttons to select a digital input (e. g. Dig. Input 3) or all four digital inputs (Dig.
Input 1…4). Press "
↵
" to confirm your selection.
Adjusting the settings:
If the digital input function is selected, then the recommended response value is
automatically adjusted:
- Test, H/A
24V (cannot be changed)
- no2->1, 1<->2, bypass, alarm and R-OPL
0 V (can be changed)
Menu
Meaning
Exit
Leave the settings menu "Digital menu; go up one menu level
Dig. Input: 3
Exit
1.Mode: off
2.Resp.val.: 24.0V
Dig. Input: 1..4
Exit
1.Mode: off
2.Resp.val.: 24.0V
Setting one digital input
Setting all digital inputs
Summary of Contents for ATICS-2-63A-DIO
Page 22: ...System description 22 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 44: ...Commissioning settings and testing 44 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 58: ...Operation 58 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 86: ...Troubleshooting 86 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 95: ...95 ATICS DIO_D00080_01_M_XXEN 04 2015 10 Data 10 1 T V test report...