Operation
51
ATICS-DIO_D00080_01_M_XXEN/04.2015
6.2.4.2
Test menu 2: Manual changeover
Manual changeover
Test of the changeover function. The device changes to the redundant line
and remains in this switch position. The changeover period t(1->2) is dis-
played. The device does not change back to the preferred line until the "RE-
SET" button has been pressed.
Cancel
Back to test menu
The date of the test is saved in the test logger to remember the next test once the test interval has
elapsed. The messages from this test are also stored in the history memory.
Risk that the test is accidentally not terminated
If the test menu 3: "Manual changeover" is left after changing over to the redun-
dant line, then the ATICS® remains in this switch position and in "TEST" mode.
- Wait until "Quit: RESET" appears on the display.
- Press the "RESET" button.
- Check whether the ATICS® has changed to the preferred line.
Manual mode aborts manual test
When the transparent cover is opened after changing over to the redundant line,
the ATICS® switches to manual mode. The test will be aborted.
After closing the transparent cover, the ATICS® switches back to the preferred
line.
No
entry will be stored in the test logger.
Manual changeover
Cancel
Manual changeover
TEST
t(1->2):
346ms
t(Test):
--
Quit: RESET
CAUTION
Summary of Contents for ATICS-2-63A-DIO
Page 22: ...System description 22 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 44: ...Commissioning settings and testing 44 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 58: ...Operation 58 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 86: ...Troubleshooting 86 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 95: ...95 ATICS DIO_D00080_01_M_XXEN 04 2015 10 Data 10 1 T V test report...