4.2.8
Fastening, inserting and securing connections
Connect the terminals according to the wiring diagram to the plug connectors (A, B) and the connec-
tor plugs (C, D).
Connect the Lines 1, 2 and 3 to the plug connectors (A,B). Consider a stripping length of 20 mm
and do not use ferrules. Use a Torx® screwdriver T20 or a slotted screwdriver of 6.5 x 1.2 mm.
Tightening torque: 2.5…4.5 Nm.
Connect the connector plugs (C) with a slotted screwdriver of 2.5 x 0.4 mm. Stripping length: 7
mm. Tightening torque: 0.22…0.25 Nm.
Insert bottom green plug connector
(B) and secure with mounting screws.
ATICS-2-DIO:
After that, insert top
green plug connector (A) and secure
with mounting screws.
ATICS-4-DIO:
After that, insert the
two top green plug connectors and
secure with mounting screws.
Insert the three connector plugs (C).
ATICS-4-DIO only:
Insert the connector plug (D) of the
measuring current transformers T1 …
T4 (D).
Note:
The plug must noticeably click into
place!