3.4 ATICS® tasks
The ATICS® transfer switching device has the following capabilities:
Two-pole changeover of the power supply
Voltage monitoring for the preferred supply (Line 1)
Voltage monitoring for the second supply (Line 2)
Voltage monitoring at the transfer switching device output (Line 3)
Monitoring of the changeover switch for correct switch position
Internal functional testing, including checking the switching times
Communication to remote MK… alarm indicator and test combinations, and to TM… alarm
indicator and operator panels via BMS bus
Option for adjusting the time delay for the changeover process according to DIN VDE 0100-710
(VDE 0100 Part 710)
Possible field of application on systems according to DIN VDE 0100-710 (VDE 0100 Part 710)
with a changeover period ≤ 15 s or even ≤ 0.5 s
3.5 The ATICS® functions
3.5.1
The transfer switching device
If the preferred supply fails, the ATICS® ensures the power supply is changed over safely.
The switch contacts are offset on a rotating shaft. This design prevents simultaneous switching of
Line 1 and Line 2. The switch has three positions:
1
Line 1 switched on
0
Both lines switched off
2
Line 2 switched on
Either Line 1 or Line 2 can be set as the preferred line (setting described in "Settings menu 1: Change-
over" on page 67 or "Settings menu 5: Digital Input" on page 73).
1. In the normal condition (fault-free condition) the preferred supply is connected. The ATICS®
will switch to the redundant line if:
– the preferred line fails
– the "TEST" button is pressed
– a digital input is configured to "TEST" and this input is enabled
– the setting "Preferred Line" is reconfigured to the other line
2. The ATICS® switches from the redundant line back to the preferred line if
– the voltage on the preferred line is restored and
- the return transfer delay time t(2->1) has expired and no switching back interlocking
function is enabled
- or immediately after pressing the "RESET" button or when the redundant line fails
(even when the switching-back interlocking function is enabled)
– the setting "Preferred Line" is reconfigured to the other line
– the digital input is configured to "TEST" and this input is reset
– a transfer switching device test is enabled and the test time has expired
Summary of Contents for ATICS-2-63A-DIO
Page 22: ...System description 22 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 44: ...Commissioning settings and testing 44 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 58: ...Operation 58 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 86: ...Troubleshooting 86 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 95: ...95 ATICS DIO_D00080_01_M_XXEN 04 2015 10 Data 10 1 T V test report...