Menu mode: Operation and setting
80
ATICS-DIO_D00080_01_M_XXEN/04.2015
7.3.5
Menu 5: Control
This menu offers various options for controlling individual devices or the overall system:
7.3.6
Menu 6: Digital Input
The voltage level of the digital inputs 1…4 are displayed on this menu.
Exit
"Digital Input" menu; go up one menu level.
--
The digital input is switched off.
1…4
Number of the digital input
0V
The response condition is not met. The input is not set. The set function has
not been carried out.
24.0V
The response condition has been met and the response delay has elapsed.
The input is set. The set function is being carried out.
7.3.7
Menu 7: Info
This menu displays information about the device and the software. Press the "
" arrow button sev-
eral times to display all the information. Please have this information to hand if you need to contact
us for assistance by telephone.
You can also reach the "INFO" menu by choosing standard display and then pressing the "INFO" but-
ton on the front panel of the device.
Line 1:
Device type
Line 2:
Date, time
Line 3:
Address set on the BMS bus
Line 4:
Serial number of the device
Line 5…8:
Software versions of the three controllers of the device
Line 9…11:
Bender address, homepage
Line 11:
Exit. Exit standard information.
Menu item
Function
Page
Exit
Exit "Control" menu; go up one menu level
1. TEST
Call up test, see chapter "6.2.4 Test function"
2. RESET
Call up a reset, see chapter "6.2.5 Reset function"
Exit
1. 0V
2. 0V
3. 0V
ATICS2-DIO-63
02.03.11 14:59
Address:3
No.: 1234567890
Summary of Contents for ATICS-2-63A-DIO
Page 22: ...System description 22 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 44: ...Commissioning settings and testing 44 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 58: ...Operation 58 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 86: ...Troubleshooting 86 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 95: ...95 ATICS DIO_D00080_01_M_XXEN 04 2015 10 Data 10 1 T V test report...