Operation
55
ATICS-DIO_D00080_01_M_XXEN/04.2015
6.2.5
Reset function
A reset is used to reset the alarm and fault messages for the device and for releasing the switching-
back interlocking function of the changeover switch. There are several ways to call up a test menu:
Select standard display and then press the "RESET" button on the front panel of the device for
at least one second.
Call the "RESET" function in the Control menu. Reset menu:
Select:
6.2.5.1
Reset menu 1: Alarm
Delete
Resets alarm and fault messages on the device. The progress of the test is
shown on the display.
The reset is required if one or more alarm-triggering parameters are not con-
stantly monitored so that the end of the alarm condition was not detected.
Cancel
Back to reset menu
For all pending alarms, the date and time of the reset are entered in the line "to" in the history mem-
ory. The "ALARM" LED goes out.
If the fault persists, a new entry is written in the history memory. The "ALARM" LED is still lit up.
Menu item
Function
Page
1. Alarm
Resets alarm and fault messages on the device.
2. SwitchBackLock.
Reactivates the switching-back interlocking function for the change-
over function. The device changes back to the redundant line.
3. Changeover
Change alarm value for the:
- maximum number of changeover operations performed
- maximum number of operating hours
- maximum number of changeover operations performed
which were carried out with overcurrent or short-circuit current
Exit
1.Alarm
2.SwitchBackLock.
3.Changeover
Delete
Cancel
Delete
Summary of Contents for ATICS-2-63A-DIO
Page 22: ...System description 22 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 44: ...Commissioning settings and testing 44 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 58: ...Operation 58 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 86: ...Troubleshooting 86 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 95: ...95 ATICS DIO_D00080_01_M_XXEN 04 2015 10 Data 10 1 T V test report...