Operation
50
ATICS-DIO_D00080_01_M_XXEN/04.2015
6.2.4.1
Test menu 1: Autom. changeover
Autom. changeover
Test of the changeover function. The device changes to the redundant line.
The changeover period t(1->2) is displayed. After the set time t(Test) has
elapsed, the device changes back to the preferred line.
Cancel
Back to test menu
The date of the test is saved in the test logger to remember the next test once the test interval has
elapsed. The messages from this test are also stored in the history memory.
If manual mode is selected for changeover (transparent cover open or digital in-
put set to "manual changeover") then no changeover can take place under the
test menu "Autom. changeover" or "Manual changeover". ATICS® then displays
the following fault alarm:
The device must be in automatic mode for a test.
During an "Autom. changeover" or "Manual changeover" test, the changeover
period t(1->2) is displayed. This is the time required for changing over from the
preferred line to the redundant line. This time may differ from the return transfer
time! Also see "Time diagram: Changeover between the preferred and redundant
line" on page 16.
Info
TEST
Cancel
Autom. changeover
Cancel
Autom. changeover
TEST
t(1->2):
457ms
t(Test):
10s
Quit: RESET
Summary of Contents for ATICS-2-63A-DIO
Page 22: ...System description 22 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 44: ...Commissioning settings and testing 44 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 58: ...Operation 58 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 86: ...Troubleshooting 86 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 95: ...95 ATICS DIO_D00080_01_M_XXEN 04 2015 10 Data 10 1 T V test report...