Installation and connection
37
ATICS-DIO_D00080_01_M_XXEN/04.2015
4.3 Other functions
4.3.1
Sealing the transparent cover of the changeover switch
4.3.2
Manual mode
The transparent cover can only be sealed
when it is closed (automatic mode).
Risk of injury from rotating Allen key
When the transparent cover is closed, the ATICS® is in automatic mode. The
ATICS® detects this by the button which is pressed under the transparent cover.
When the transparent cover is opened, the button is no longer pressed and the
ATICS® switches to manual mode.
When the transparent cover is open, make sure that this button is not pressed ac-
cidentally. Check and make sure that the message "Manual mode" appears on
the display. Only then can the Allen key be used to set the changeover switch to
manual mode.
Manual mode can be enabled in the fol-
lowing ways:
Open the transparent cover
Set the digital input. "M/A" function
must be set (see "Settings menu 5:
Digital Input" on page 73).
Manual mode:
Put the handle on the Allen key
Use the Allen key to change over
The switch position "0" of the
changeover switch can be locked
with a padlock
CAUTION
Summary of Contents for ATICS-2-63A-DIO
Page 22: ...System description 22 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 44: ...Commissioning settings and testing 44 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 58: ...Operation 58 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 86: ...Troubleshooting 86 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 95: ...95 ATICS DIO_D00080_01_M_XXEN 04 2015 10 Data 10 1 T V test report...