Troubleshooting
82
ATICS-DIO_D00080_01_M_XXEN/04.2015
8.1.2
Messages with error code or service code
Phase sequence
This line does not have a right
phase sequence. If the direction of
the phase sequence of Line 1 is
different from Line 2, it may result
in malfunctions or failure on
connected three-phase devices.
- Install Line 1 and Line 2 in a way that the di-
rection of the phase sequence of both lines
is clockwise (right).
Error during the
changeover process
When the test set-ups do not
supply enough current for
switching the coils of the ATICS
- Only use test set-ups that provide the nec-
essary peak current of 17 A.
Error code/
Service code
Description
Remedy
1.xx, 4.xx, 9.xx
Fault message from the internal memory
monitoring.
- Contact Bender Service.
3.11
Maximum number of operating hours
exceeded.
- Plan device replacement. Alarm can be
cancelled (see "Reset menu 3: Changeo-
ver" on page 57).
3.12
Maximum number of changeovers
exceeded.
- Plan device replacement. Alarm can be
cancelled (see "Reset menu 3: Changeo-
ver" on page 57).
3.13
Changeover due to overcurrent or short-
circuit detected. These changeovers
reduce the life of the device. Currents
which are measured in excess of 150 times
the rated current are evaluated as overcur-
rents or short-circuit currents.
- Have personnel assess the short-circuit
load. Contact Bender Service. Alarm can
be cancelled (see "Reset menu 3:
Changeover" on page 57).
3.5
Service was carried out. This is not a fault
message. Only displayed in the service
logger menu.
- No action required
6.xx, 7.xx, 8.1x
Device error. The internal self monitoring
of the device has detected a fault which
could impair the safe operation of the
device.
- Device is to be replaced without delay.
8.51 … 8.52
Fault internal power supply unit.
- RESET -> execute alarm, then test the
changeover function.
- If fault persists:
device replacement.
- Only use test set-ups that provide the
necessary peak current of 17 A.
Fault/message
Description
Remedy
Summary of Contents for ATICS-2-63A-DIO
Page 22: ...System description 22 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 44: ...Commissioning settings and testing 44 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 58: ...Operation 58 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 86: ...Troubleshooting 86 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 95: ...95 ATICS DIO_D00080_01_M_XXEN 04 2015 10 Data 10 1 T V test report...