81
ATICS-DIO_D00080_01_M_XXEN/04.2015
8. Troubleshooting
8.1 Fault and alarm messages
In the event of an alarm, the messages of the ATICS® will enable you to narrow down the possible
causes. Some messages may point to several causes. The following possible faults are indicated by
messages on the ATICS® display:
Plain text fault messages
Fault messages with error code
8.1.1
Plain text fault messages
Fault/message
Description
Remedy
Failure Line xx
(xx stands for: 1, 2,
AV, SV, UPS, BSV),
undervoltage or
overvoltage
Voltage is no longer available on
Line 1 or Line 2
(Channel 1 = Line 1,
Channel 2 = Line 2)
- Measure voltage on Line xx.
- Check cause.
- Eliminate fault on the system.
- Check the setting for voltage and hystere-
sis.
Failure Line 2
Generator delivers no voltage
within the set time
Device error +
Errorcode
For details about actions to be taken refer to table section "Error code/service
code". The message is on channel 6 of the BMS bus.
Short-circuit
distribution board
Short-circuit detected
- Eliminate short-circuit
Failure distribution
board
No voltage on Line 3, contact of
the changeover switch defective
- Replace the ATICS®.
Overcurrent I(3)
Measuring current transformer T3
resp. one of the measuring current
transformers T3…T6 recognised
an overcurrent
- Eliminate the cause of overcurrent.
- Eliminate any damage.
CT connection
CT short-circuit
Measuring current transformer T3
resp. T3…T6, channel 7
- Check connecting wire of the measuring
current transformer(s).
No MASTER
There is no device with master
function or back-up master (device
with address "1") available on the
RS-485 interface
- Check BMS bus connection cable.
- Check whether master has failed or wheth-
er its address has changed
Service: __ (date)
Reminder for next service
- Agree date with Bender Service
Test:
__ (date)
Reminder for next test
- Plan date for test.
- Carry out test.
Manual mode
Message "Manual mode" although
manual mode has not been
activated
- Check the connections of the digital input
Summary of Contents for ATICS-2-63A-DIO
Page 22: ...System description 22 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 44: ...Commissioning settings and testing 44 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 58: ...Operation 58 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 86: ...Troubleshooting 86 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 95: ...95 ATICS DIO_D00080_01_M_XXEN 04 2015 10 Data 10 1 T V test report...