Periodic verification and service
89
ATICS-DIO_D00080_01_M_XXEN/04.2015
Conditions for operation with the bypass switch
Wiring must be carried out according to "Connection example: ATICS-2-DIO with bypass
switch" on page 33 resp. "Connection example: ATICS-4-DIO with bypass switch" on page 34.
The following settings are to be set in the "Settings menu 5: Digital Input" menu:
Dig. Input 1:
– 1. Mode:
Bypass
– 2. Resp. value:
0 V
– 3. t(on) Response delay:
100 ms
– 4. t(off) Delay on release:
100 ms
9.6 Replace the ATICS®
The plug connectors make it easy to replace the device if
the ATICS® has reached the end of its useful life or
an event has occurred which jeopardises safety: e.g. overvoltage, switching if there is a short-
circuit or component failure.
Risk of electric shock when touching the contacts on Line 1
Mains voltage at the contacts of Line 1.
Plug must not be touched unless the part is isolated.
Risk of fatal injury from electric shock
Touching live parts of the system carries the risk of electric shock.
Before fitting the enclosure and working on the device connections, make sure
that the power supply has been disconnected and the system is dead.
If ATICS® is bypassed by an ATICS-BP-… bypass switch, then the regulations
which apply to working on live parts must be followed.
WARNING
DANGER
Summary of Contents for ATICS-2-63A-DIO
Page 22: ...System description 22 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 44: ...Commissioning settings and testing 44 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 58: ...Operation 58 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 86: ...Troubleshooting 86 ATICS DIO_D00080_01_M_XXEN 04 2015...
Page 95: ...95 ATICS DIO_D00080_01_M_XXEN 04 2015 10 Data 10 1 T V test report...