Installation
Instruction handbook
b maXX
5000
Document No.: 5.09021.16
141
7
7.12 Installation procedure
DANGER!
Risk of fatal injury from electrical current!
Electrically live parts are life-threatening.
Therefore:
m
Make certain that the parts to be mounted (e.g. mains cables) and the mounting
areas are de-energized for the entire duration of mounting the device.
h
Route all cables in an EMC-compatible manner.
h
(Observe the permissible torques!)
h
For all connections, attentions is to be paid to strain relief
The installation comprises the following steps:
1
Connect the motor through terminals 1U2, 1V2, 1W2 and PE.
Ensure the proper phases when connecting (rotational direction).
Observe the permissible torques!
NOTICE!
Internal overload protection operates exceeding 200 % of the motor rated current (full
load current).
2
Connect the DC link - only for
BM53XX
, refer to
3
Connect fuses (F1) - not for
BM53XX
(if UL 508C is being considered, the UL-listed semiconductor or entire area fuses stat-
ed in Chapter
as from page 261 are to be used).
4
Connect the main contactor - not for
BM53XX
5
Connect the line filters (Z1) - not for
BM53XX
.
6
Connect the choke (L1) to the mains filter output (not necessary for
BM53XX
).
7
Connect devices to the mains choke output via the mains input terminals 1U1, 1V1
and 1W1 - not with
BM53XX
.
The mains cable has to be laid through the toroidal cores to ensure an operation within
a C2 environment (see also
8
Connect the protective ground conductor to the PE terminal (a fixed ground conductor
connection is absolutely mandatory).
9
Connect 24 V power supply:
BM50XX, BM51XX, BM53XX
via terminals X200 -1, X200 -2
(if UL 508C is being considered, then the current is limited to 4 A).
10
Connect the signal bus cable (see