Cabling
Instruction handbook
b maXX
5000
Document No.: 5.09021.16
Baumüller Nürnberg GmbH
260
11.1
SIE
The connection cable is not offered by Baumüller and must be made by the user:
1
Use the following materials:
m
Cable: LiYCY 2 x (2 x 0.14 mm²) + 1x0.34 mm² Cu braiding.
m
D-sub connector: 9-pin, female (SIE side)
m
E.g. D-sub connector: 26-pin, male (
b maXX 5000
side)
m
Cables must be of twisted pair wire (DAT+/DAT-, CLK+/CLK-) from SSI encoder em-
ulation to further master control systems
2
Connect
m
the cable shield with the connector shell of the D-sub male/D-sub female connector
m
the 9-pin female connector (SIE side) with the cable
m
e.g. the 26-pin D-sub male connector (
b maXX 5000
side, pin assignment see
Connecting cable for sine/square-wave incremental encoder
on page 258) with
the other cable ending.
NOTE!
On the SSI encoder emulation side data and clock cables (DATA+/DATA- and CLK+/
CLK-) are terminated with 120
. Additional termination resistors are required on the
CNC side if this resistors are not provided by its manufacturer.
1
5
9
8
7
1
20
19
13
3
Figure 115:
Connection cable IEE with
b maXX
5000