Operating conditions
Instruction handbook
b maXX
5000
Document No.: 5.09021.16
Baumüller Nürnberg GmbH
48
3.3
3.3.5
Correction values at changed operating conditions
The correction values of the permitted output power and output current must be multi-
plied, if the devices
b maXX
5000
are used at operation conditions with different correc-
tion values.
The following correction values are to be considered if nothing other is specified at the
„Electrical data“ of the device:
NOTE!
Baumüller devices that are intended for operation in grounded delta mains or IT
mains may only be operated in those types of mains up to an installation altitude of
2000 m above MSL. At an installation altitude of 2000 m and higher these devices are
to be operated in TN and TT mains. Power supply of this type can be accomplished
by using an isolating transformer with a secondary-side grounded neutral point, for
example.
NOTE!
The temperature of the water cooler or the cold plate temperature must be higher or
equal to the surrounding temperature to prevent condensation.