![Baumuller b maXX 5000 Instruction Handbook Manual Download Page 304](http://html.mh-extra.com/html/baumuller/b-maxx-5000/b-maxx-5000_instruction-handbook-manual_2711361304.webp)
Electrical data BM5030 with safety function
Instruction handbook
b maXX
5000
Document No.: 5.09021.16
Baumüller Nürnberg GmbH
304
C.3
C.3
Electrical data BM5030 with safety function
BM50
30
with safety function
BM5030-XX
2
X-...
Input rated power
1)
6 kVA
Input rated current (I
eff
)
1) 2) 3)
12 A
Distortion factor of the input current (THD
I
)
1)
110 % ± 10 %
Input peak current (I
eff
)
1) 2) 3)
12.5 A
for max. 150 s
DC link voltage, power supply dependent/rated
540 V
DC
at U
power supply
= 3 x 400 V
Internal DC link capacitance C
int
330 µF,
internal - connected upstream the STO
DC link discharge time (C
int
)
8)
Approx. 900 s
Maximum connectable DC link capacitance (external) C
ext
200 µF,
external - connected downstream the STO
DC link discharge time (C
ext
)
10)
80 ms
Total maximum connectable capacitance in the DC link
3.15 mF,
in external
connected upstream the STO 9)
Waiting time between 2 charging processes
with external connected capacitance
t
C
int
C
ext
+
U
power supply
2
2 60 W
--------------------------------------------------------------------------------
Connection power at DC link
1) 5)
5 kW
Peak power at DC link
4) 6)
7.5 kW
for max. 150 s
Ready-to-operate after
7 s
Max. charge-up time
10 s
External brake resistor R
B
No connection
External brake resistor continuous power
-
Quick discharge resistor
-
Power loss with regard to power supply
50 W
Power loss with regard to control voltage supply
7)
Max. 25 W
Cooling air requirement power heat sink
40 m
3
/h
Cooling air velocity power heat sink
-
Cooling air requirement internal space of device
8 m
3
/h