WARNING!
Risk of injury due to insufficient qualifications!
Inevitably, when operating this electrical device, certain parts of this device are ener-
gized with hazardous voltage. Improper handling can lead to significant personal in-
jury and material damage.
Therefore:
m
Only qualified personnel may work on this device!
Operating concept
Instruction handbook
b maXX
5000
Document No.: 5.09021.16
Baumüller Nürnberg GmbH
204
8.1
8.1
Operating concept
After the device has been commissioned it is parameterized (i. e. adapted to the applica-
tion). Once parameterization has been completed, the device can be operated with one
of the two following signal inputs:
m
pulse enable
m
quick stop (option)
8.1.1
Release signals
These signals must have a signal level of 24 V (DC) and be available via the terminals
(
Pulse enable
During operation, the „pulse enable“ signal must be continuously generated in order for
the device to provide output. A running motor will come to a standstill if the signal is
switched to 0 V.
Quick stop
Only switch off the „quick stop“ signal if the system / the device must be stopped as quick-
ly as possible. The reaction can be adjusted (see the parameter manual)
During operation, the „quick stop“ signal must be continuously provided in order for the
device to provide output.
Exactly which digital input can be assessed as a quick stop signal can be parameterized.
(Refer to the parameter manual
b maXX
5000
5.09022)