DANGER!
Risk of fatal injury due to high leakage current!
The cross-section of the protective ground conductor must be at least 10 mm²
(EN 61800-5-1, Chapter 4.3.5.5.2).
BFN 3-1- ... -001
0007
0016
0030
0042
0056
0075
0100
0130
Max. power supply voltage
3 x 480 V
AC
+10%, 50/60 Hz
Rated current (at T
B
=
40 °C)
7.6 A
17.5 A
33 A
46 A
70 A
82 A
109 A
142 A
Rated current (at T
B
=
50 °C)
7 A
16 A
30 A
42 A
56 A
75 A
100 A
130 A
Peak current
1.5 x I
N
for < 1 min per hour
Max. voltage
Outer conductor/GND
Neutral point of the outer conductor/GND
305 V
AC
0 V
Max. test voltage
line to line
line to case
2.1 kV
DC
for 2 s at 25 °C
2.7 kV
DC
for 2 s at 25 °C
Maximum connection cross-section
4
mm²
4
mm²
10
mm²
10
mm²
16
mm²
25
mm²
50
mm²
50
mm²
Power loss (typical)
4 W
8 W
12 W
15 W
18 W
24 W
24 W
30 W
Harmonic frequencies (mains voltage)
THD
U
< 10%
Protection rating
IP 20
Weight
0.6 kg
1.0 kg
1.3 kg 1.6 kg 1.9 kg 2.6 kg
4.0 kg 4.2 kg
BFN 3-1-... -001
0020
EPCOS
B84143A0150R410
LGF
FFU 3x295AB-SBM
Max. power supply voltage
3 x 480 V
AC
+10 %, 50/60 Hz
Rated current (at T
B
=
40 °C)
20 A
150 A
295 A
Peak current (at T
B
= 40°)
1.5 x I
N
for < 3 min per hour
1.5 x I
N
for < 60 s per hour
Max. voltage
outer conductor/GND
neutral point of the outer conductor/GND
305 V
AC
0 V
Max. test voltage at 25 °C
line to line
line to case
2.1 kV
DC
at 25 °C for 2 s
2.2 kV
DC
for 2 s
2.7 kV
DC
for 2 s
2.1 kV
DC
for 2 s
2.7 kV
DC
for 2 s
Maximum connection cross-section
95 mm²
Harmonic frequencies (mains voltage)
THD
U
< 10 %
Protection rating
IP 20
Weight
13.5 kg
Accessories and spare parts
Instruction handbook
b maXX
5000
Document No.: 5.09021.16
273