![Baumuller b maXX 5000 Instruction Handbook Manual Download Page 291](http://html.mh-extra.com/html/baumuller/b-maxx-5000/b-maxx-5000_instruction-handbook-manual_2711361291.webp)
Shutdown, Storage
Instruction handbook
b maXX
5000
Document No.: 5.09021.16
291
12
1
Secure the device against falling off/out.
2
Loosen all mechanical connections.
3
Lift the device out of the control cabinet.
4
Store the device in a suitable packing.
5
At transportation pay attention to, that the device is not damaged by wrong storage or
severe shocks, also see
What to observe when transporting
In case you want to dispose the device, additional data is available in chapter
12.5 Storage conditions
The device is maintenance-free. If you keep to the environmental conditions during the
entire period of storage, you can assume, that the device will not be damaged. In case
the environmental conditions during storage are not kept, you should assume that the de-
vice is damaged after storage.
NOTICE!
Property damage because of incorrect storage conditions
Incorrect storage can damage/destroy the device.
Therefore:
Assure, that the environmental conditions are kept during the entire period of storage:
m
Climatic category 1K4
m
Temperature range -25 °C to +55 °C
NOTICE!
Recommissioning without forming of the capacitors.
From six months storage period on, the capacitors are destroyed during commission-
ing, if they are not formed beforehand
m
Reform the DC link capacitors:
n
by supplying the device ready-to-operate for at least one hour with supply volt-
age
n
but do not enable pulses during this time.
m
Consider, that it is imperative, to connect the accordingly prescribed line commu-
tating chokes for this forming procedure. Devices, where no line commutating
chokes is necessary can directly be supplied with mains voltage.