Technical data
Instruction handbook
b maXX
5000
Document No.: 5.09021.16
59
3
m
BM50
30
mains rectifier unit with safety function
NOTE!
Description of BM5030 with safety function
BM5030-XX
2
X-...
refer to
C.3 Electrical data BM5030 with safety function
m
BM50
3
X mains rectifier unit
without safety function
BM50
31
BM50
31-A
BM50
31
BM50
31-A
-
X
T0
X
-.. /-
X
I0
X
-.. / -
X
G0
X
-..
without charge resistor
-
X
R0
X
-.. /-
X
S0
X
-.. / -
X
W0
X
-..
with charge resistor
Input rated power
1)
12 kVA
17.5 kVA
14)
Input rated current (I
eff
)
1) 2) 3)
17 A
25 A
Distortion factor of the input current (THD
I
)
1)
57 % ± 10 %
180 % ± 10 %
Input peak current (I
eff
)
1) 2) 3)
25 A for max. 150 s
37.5 A for max. 150 s
DC link voltage
power supply dependent/rated
540 V
DC
at U
supply
= 3 x 400 V
DC link capacitance (internal)
940 µF
DC link discharge time
(internal DC link capacitance)
9)
Approx. 450 s
Total max. connectible capacitance in the
DC link (in external)
20 mF
Connection power at DC link
1) 5)
10 kW
18 kW
Peak power at DC link
4) 6)
15 kW for max. 150 s
27 kW for max. 150 s
Ready-to-operate after
7 s
Max. charge-up time
10 s
Quick discharge
10)
5 s
External brake resistor R
B
R
B
33
External brake resistor continuous power
18 kW
Quick discharge resistor
-
Power loss with regard to power supply
7)
40 W
80 W
Power loss with regard to control voltage
supply
8)
Max. 10 W
Cooling air requirement power heat sink
40 m
3
/h
-
40 m
3
/h
-
Cooling air velocity power heat sink
-
> 5 m/s
-
> 5 m/s
Cooling air requirement internal space of
device
8 m
3
/h
Footnotes refer to