148
Technical data • Individual components
Automation PC 620 User's Manual V 1.90
The following bus lengths are permitted with a maximum oscillator tolerance of 0.121 %:
The material used for the cable should preferably have all or most of the following properties in
order to reach an optimal transfer rate.
Terminating resistance
CAN networks are cabled using a bus structure where both ends of the bus are equipped with
terminating resistors. The add-on CAN interface has an integrated terminating resistor (delivery
state: disabled with the setting "Off").
Distance [m]
Transfer rate [kBit/s]
≤
1000
Type 50
≤
200
Type 250
≤
60
Type 500
Table 74: CAN bus length and transfer rate
CAN cable
Property
Signal lines
Cable cross section
Wire insulation
Conductor resistance
Stranding
Shield
2 x 0.25 mm² (24AWG/19), tinned Cu wire
PU
≤
82 Ohm / km
Wires stranded in pairs
Paired shield with aluminum foil
Grounding line
Cable cross section
Wire insulation
Conductor resistance
1 x 0.34 mm² (22AWG/19), tinned Cu wire
PU
≤
59 Ohm / km
Outer sheathing
Material
Properties
Entire shielding
PUR mixture
Halogen free
From tinned cu wires
Table 75: CAN cable requirements
Figure 66: Terminating resistor for add-on CAN interface 5AC600.CANI-00
ON
OFF
Summary of Contents for Automation PC 620
Page 2: ...2 Automation PC 620 User s Manual V 1 90...
Page 4: ...4 Automation PC 620 User s Manual V 1 90...
Page 6: ...6 Automation PC 620 User s Manual V 1 90...
Page 376: ...376 Maintenance servicing International certifications Automation PC 620 User s Manual V 1 90...
Page 487: ...Appendix A Glossary Appendix A 487 Automation PC 620 User s Manual V 1 90...
Page 488: ...488 Appendix A Glossary Automation PC 620 User s Manual V 1 90...
Page 512: ...Index 512 Automation PC 620 User s Manual V 1 90...