364
Maintenance / servicing • Requirements for immunity to disturbances
Automation PC 620 User's Manual V 1.90
4.7 Voltage dips, fluctuations and short-term interruptions
4.8 Damped oscillations
Test carried out according to
EN 61000-4-11
Limits according to
EN 61000-6-2
Limits according to
EN 61131-2
Limits according to
EN 55024
AC power inputs
Voltage dip
70 % (30 % reduction), 0.5
periods, criteria B
-
Voltage dip
< 5 % (> 95 % reduction), 0.5 half-
oscillations, criteria B
AC power inputs
Voltage dip
40 % (60 % reduction), 5 periods,
criteria C
-
Voltage dip
70 % (30 % reduction), 25 half-
oscillations, criteria C
AC power inputs
Voltage dip
40 % (60 % reduction), 50
periods, criteria C
-
-
AC power inputs
Voltage interruptions
< 5 % (> 95 % reduction), 250
periods, criteria C
-
Voltage interruptions
< 5 % (> 95 % reduction), 250
half-oscillations, criteria C
AC power inputs
-
20 interruptions, 0.5 periods,
criteria A
-
DC power inputs
-
20 interruptions for 10 ms < UN -
15 %, criteria A
-
Table 258: Test requirements - voltage dips, fluctuations, and short-term interruptions
Test carried out according to
EN 61000-4-12
Limits according to
EN 61131-2
Power I/O, L to L
± 1 kV, 1 MHz, repeat rate
400/seconds, length 2 seconds,
connection lengths 2 m, criteria B
Power I/O, L to PE
± 2.5 kV, 1 MHz, repeat rate
400/seconds, length 2 seconds,
connection lengths 2 m, criteria B
Table 259: Test requirements - damped vibration
Summary of Contents for Automation PC 620
Page 2: ...2 Automation PC 620 User s Manual V 1 90...
Page 4: ...4 Automation PC 620 User s Manual V 1 90...
Page 6: ...6 Automation PC 620 User s Manual V 1 90...
Page 376: ...376 Maintenance servicing International certifications Automation PC 620 User s Manual V 1 90...
Page 487: ...Appendix A Glossary Appendix A 487 Automation PC 620 User s Manual V 1 90...
Page 488: ...488 Appendix A Glossary Automation PC 620 User s Manual V 1 90...
Page 512: ...Index 512 Automation PC 620 User s Manual V 1 90...