AUX DC Inverter Free Match 50HZ R410A
Ceiling & Floor Type
24
2. Specfication
Model
Indoor
Unit
AMCF-H09/4R1
AMCF-H12/4R1
AMCF-H18/4R1
Capacity
Cooling
Btu/h
9560(5120-12115)
12285(5800-12625)
18080(8530-19107)
kW
2.80(1.50-3.55)
3.60(1.70-3.70)
5.3(2.50-5.6)
Heating
Btu/h
10240(5460-13000)
13306(6930-15080)
19790(10340-24000)
kW
3.00(1.60-3.81)
3.9(2.03-4.42)
5.8(3.03-7.03)
Electric
Data
Power Supply
V~,Hz,Ph
220~240,50,1
220~240,50,1
220~240,50,1
Cooling Power Input
W
80(20-125)
80(20-125)
80(20-125)
Heating Power Input
W
80(20-125)
80(20-125)
80(20-125)
Fan Motor
Model
/
YSK-25W-4
YSK-25W-4
YSK-40W-4
Output Power
W
25
25
40
Capacitor
uF
1.5
1.5
2.5
Speed (Hi/Mi/Lo)
r/min
1030/866/735
1030/866/735
1250/1100/900
Indoor Coil
Number Of Row
/
2
2
3
Tube Pitchx Row Pitch
mm
20.5x 12.7
20.5x 12.7
20.5x 12.7
Fin Pitch
mm
1.6
1.6
1.6
Fin Material
/
Hydrophilic aluminum
Hydrophilic aluminum
Hydrophilic aluminum
Tube Outside Dia.&
Material
mm
φ7
,
Inner grooved
φ7
,
Inner grooved
φ7
,
Inner grooved
Coil L x H x W
mm
599x246x 25.4
599x246x 25.4
599x246x 38.1
Heat Exchanging Area
m
2
4.21
4.21
6.32
Air Flow volume
m
3
/h
620/504/441
620/504/441
850/680/595
Sound Pressure Level
dB(A)
39/36/30
39/36/30
43/39/36
Dimension
Net Dim(W*D*H)
mm
929×660×205
929×660×205
929×660×205
Packing Dim(W*D*H)
mm
1010×720×290
995×710×280
995×710×280
Weight
Net
kg
24
24
25
Gross
kg
27
27
28
Refrigerant Type
/
R410a
R410a
R410a
Pipe Dia
Liquid Side
mm(inch)
6.35(1/4)
6.35(1/4)
6.35(1/4)
Gas Side
mm(inch)
12.7(1/2)
12.7(1/2)
12.7(1/2)
Drainage
mm
20
20
20
Loading
Qty
20/40/40H
unit
136/280/315
136/280/315
136/280/315
Note:
1.Cooling capacity test Condition:(27
℃
DB,19
℃
WB Indoor/35
℃
DB,24
℃
WB Outdoor);
Heating capacity test Condition:(20
℃
DB Indoor/7
℃
DB,6
℃
WB Outdoor);
connecting pipe length: 5M.
2.Datas may be changed with unit improvement. We keep the right to change the datas or specifications
withoutprior notice, please follow the datas listed on the nameplate.
Summary of Contents for AMCA-H09/4R1A
Page 1: ...AUX DC Inverter Free Match 50HZ R410A 1 SERVICE MANUAL DC Inverter Free Match R410a ...
Page 80: ...AUX DC Inverter Free Match 50HZ R410A Free Match outdoor unit 80 ...
Page 107: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 107 Outdoor protection phase sequence ...
Page 108: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 108 Cooling high pressure protection ...
Page 109: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 109 Heating high pressure protection ...
Page 110: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 110 Cooling low pressure protection ...
Page 111: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 111 Heating low pressure protection ...
Page 115: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 115 Sensor failure protection ...
Page 117: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 117 Poor effect ...
Page 118: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 118 ...
Page 119: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 119 Abnormal sound or viberation ...
Page 120: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 120 ...
Page 121: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 121 Abnormal odor ...
Page 123: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 123 Air conditioner water leakage ...
Page 132: ...AUX DC Inverter 1 Drive1 50HZ R410A Sensorresistance table 132 Wired controller XK 05 ...
Page 133: ...AUX DC Inverter 1 Drive1 50HZ R410A Sensorresistance table 133 ...