AUX DC Inverter Free Match 50HZ R410A
Free Match outdoor unit
76
Equivalent Pipe length L
=
Actual Pipe length L+ Bend Qty× Equivalent pipe bend Oil Loop Qty × Equivalent
Oil Loop length
Sample:
AM2-H18/4DR1A Actual Pipe length is 25 meters, Gas pipe diameter is 9.52
mm. If there’s 5 bends and 2 oil loops
during the installation, then the equivalent pipe length should be:
L=25+0.18×5+1.3×2=28.5(m)
◇
Specification of Connection Pipe for Indoor Unit and Outdoor Unit
Cooling Capacity(Btu/h)
18000
24000
27000
36000
42000
Connection Pipe (mm)
Liquid Pipe
Φ6.35
Gas Pipe
Φ9.52
Max. Length(Each)
15
Max. Height (m)
10
Max. Bend Qty
5
Extra R410a per meter when the pipe length is more
than 5 meter (kg)
0.022
Caution:
1. The standard Pipe length is 5m, if the pipe length is less than this then no additional charging is necessary. If the
pipe length is more than this then you should charge more refrigerant into the system according to the above
Charging Data
2. The thickness of the pipe is 0.6-1.0, bearing pressure is 4.2MPa;
3. If the connection pipe is too long, the cooling capacity and stability would be decreased. And the more bend
quantity, the resistance in the piping system would be bigger, then the cooling and heating capacity would be
decreased even lead to compressor broken. We suggest you to use the shortest connection pipe according to the
pipe length parameter in this manual.If the height difference between outdoor and indoor unit is more than 5m, an
oil trap should be installed in the gas pipe for every 10 meters.
Summary of Contents for AMCA-H09/4R1A
Page 1: ...AUX DC Inverter Free Match 50HZ R410A 1 SERVICE MANUAL DC Inverter Free Match R410a ...
Page 80: ...AUX DC Inverter Free Match 50HZ R410A Free Match outdoor unit 80 ...
Page 107: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 107 Outdoor protection phase sequence ...
Page 108: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 108 Cooling high pressure protection ...
Page 109: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 109 Heating high pressure protection ...
Page 110: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 110 Cooling low pressure protection ...
Page 111: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 111 Heating low pressure protection ...
Page 115: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 115 Sensor failure protection ...
Page 117: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 117 Poor effect ...
Page 118: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 118 ...
Page 119: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 119 Abnormal sound or viberation ...
Page 120: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 120 ...
Page 121: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 121 Abnormal odor ...
Page 123: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 123 Air conditioner water leakage ...
Page 132: ...AUX DC Inverter 1 Drive1 50HZ R410A Sensorresistance table 132 Wired controller XK 05 ...
Page 133: ...AUX DC Inverter 1 Drive1 50HZ R410A Sensorresistance table 133 ...