AUX DC Inverter Free Match 50HZ R410A
Installation
91
drainage pipe should be wrapped by additional 10~30 mm thick insulation material.
Seal the hole on the wall.
◇
To prevent rainwater or other foreign bodies from entering the room and air-conditioner, the gap between wall hole
and tubing, drain pipe and electric wire should be sealed with mastic, sealant rubber or putty.
◇
If the outdoor unit is higher than indoor unit, tubing should be bent to ensure that the lowest point of the tubing is
lower than the wall hole to prevent rainwater entering the room or air-conditioner along the piping system.
Additional refrigerant charge
When pipe length exceeds 5m, please add refrigerant according to the table below:
Connection piping
Piping size)
Additional refrigerant charge
amount (kg/m)
Gas pipe
Liquid pipe
Piping between indoor
and outdoor unit
φ9.52×0.75mm
φ6.35×0.75mm
0.022
φ12.7×1mm
φ6.35×0.75mm
0.022
φ15.88×1mm
φ9.52×0.75mm
0.050
φ19.05×1mm
φ9.52×0.75mm
0.070
φ19.05×1mm
φ12.7×1mm
0.090
Oil grade and standard oil-filled volume of Compressor
Outdoor unit model
Brand
Compressor model
Oil type
Oil volume(cm
3
)
AM2-H18/4DR1A
GMCC
DA150S2C-30KZ
VG74
500
AM3-H24/4DR1A
GMCC
DA250S2C-30MT
VG74
820
AM3-H27/4DR1A
GMCC
DA250S2C-30MT
VG74
820
AM4-H36/4DR1
LANDA
QXAS-D32zX090B
VG74
950
AM5-H42/4DR1
LANDA
QXAS-D32zX090B
VG74
950
Others
Make sure that the oil can return to the unit smoothly.
◇
Horizontal pipes should incline toward the outdoor unit using a 20:1 slop.e
◇
If there is a height difference(
△
H) between the indoor and outdoor unit, oil loops should be installed in the inter
connecting gas (large) pipe;
When
△
H
≤
5 meters, an oil loop should be installed at thebottom of the gas (large) pipe;if the constant risedistance is too
long, an oil loop should be installed in the gas (large) pipe every 10 meters.
When
△
H
>
5 meters, then for every 5 meters an oil loop mustbe installed at the bottom of the gas (large) pipe, and a short
loop (liquid ring) should be installed at theexit of the indoor unit liquid (small) pipe;
◇
When the outdoor and indoor units are at the same elevation, If the horizontal connecting pipe length is less than 10
m,the oil deposit bend and liquid ring donot need to be installed.
If the horizontal connecting pipe length is more than 10 m, install an oil loop in the gas (large)pipe every 10 metres.
Summary of Contents for AMCA-H09/4R1A
Page 1: ...AUX DC Inverter Free Match 50HZ R410A 1 SERVICE MANUAL DC Inverter Free Match R410a ...
Page 80: ...AUX DC Inverter Free Match 50HZ R410A Free Match outdoor unit 80 ...
Page 107: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 107 Outdoor protection phase sequence ...
Page 108: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 108 Cooling high pressure protection ...
Page 109: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 109 Heating high pressure protection ...
Page 110: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 110 Cooling low pressure protection ...
Page 111: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 111 Heating low pressure protection ...
Page 115: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 115 Sensor failure protection ...
Page 117: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 117 Poor effect ...
Page 118: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 118 ...
Page 119: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 119 Abnormal sound or viberation ...
Page 120: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 120 ...
Page 121: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 121 Abnormal odor ...
Page 123: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 123 Air conditioner water leakage ...
Page 132: ...AUX DC Inverter 1 Drive1 50HZ R410A Sensorresistance table 132 Wired controller XK 05 ...
Page 133: ...AUX DC Inverter 1 Drive1 50HZ R410A Sensorresistance table 133 ...