6.6 Drainage pipe installation
The drainage pipe should be properly insulated to prevent the generation of condensation.Heat insulation
material: the thickness of rubber insulation pipe should be more than 8mm
◇
Drainage pipe must have a downward gradient (1 / 50 1 / 100) to avoid water backflow or leakage etc.
◇
The unit has a drain pump which will lift up to 1200mm. However after the pump stops the water left in
the pipe will drain back and may overflow the drain tray causing water leakage. For this reason please
install the drain pipe as shown
◇
When draining multiple units into a common drain line, this common drain should be installed about
100mm below each units drain outlet, as shown in the drawing.
◇
When finish installation please carry out the drainage test to ensure that the water flow through the
Summary of Contents for AMCA-H09/4R1A
Page 1: ...AUX DC Inverter Free Match 50HZ R410A 1 SERVICE MANUAL DC Inverter Free Match R410a ...
Page 80: ...AUX DC Inverter Free Match 50HZ R410A Free Match outdoor unit 80 ...
Page 107: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 107 Outdoor protection phase sequence ...
Page 108: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 108 Cooling high pressure protection ...
Page 109: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 109 Heating high pressure protection ...
Page 110: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 110 Cooling low pressure protection ...
Page 111: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 111 Heating low pressure protection ...
Page 115: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 115 Sensor failure protection ...
Page 117: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 117 Poor effect ...
Page 118: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 118 ...
Page 119: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 119 Abnormal sound or viberation ...
Page 120: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 120 ...
Page 121: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 121 Abnormal odor ...
Page 123: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 123 Air conditioner water leakage ...
Page 132: ...AUX DC Inverter 1 Drive1 50HZ R410A Sensorresistance table 132 Wired controller XK 05 ...
Page 133: ...AUX DC Inverter 1 Drive1 50HZ R410A Sensorresistance table 133 ...