AUX DC Inverter Free Match 50HZ R410A
Four-way cassette
10
2. Specification
Model
Indoor
Unit
AMCA-H09/4R1A
AMCA-H12/4R1A
AMCA-H18/4R1A
Capacity
Cooling
Btu/h
9560(5120-12115)
12285(5800-12625)
17060(8530-19107)
kW
2.80(1.50-3.55)
3.60(1.70-3.70)
5.0(2.50-5.6)
Heating
Btu/h
10240(5460-13000)
13306(6930-15080)
19107(10340-24000)
kW
3.00(1.60-3.81)
3.9(2.03-4.42)
5.6(3.03-7.03)
Electric Data
Power Supply
V~,Hz,Ph
220~240,50,1
220~240,50,1
220~240,50,1
Cooling Power Input
W
70(17.5-109)
70(17.5-109)
70(17.5-109)
Heating Power Input
W
70(17.5-109)
70(17.5-109)
70(17.5-109)
Fan Motor
Model
/
XD30B
XD30B
XD30B
Output Power
W
30
30
30
Capacitor
uF
2.0
2.0
2.0
Speed (Hi/Mi/Lo)
r/min
839/757/688
839/757/688
839/757/688
Indoor Coil
Number Of Row
/
2
2
2
Tube Pitchx Row Pitch
mm
20.5x 12.7
20.5x 12.7
20.5x 12.7
Fin Pitch
mm
1.5
1.5
1.5
Fin Material
/
Hydrophilic aluminum fin Hydrophilic aluminum fin Hydrophilic aluminum fin
Tube Outside Dia.&Material
mm
φ7
,
Inner grooved
φ7
,
Inner grooved
φ7
,
Inner grooved
Coil Length x Height x Width mm
1352x205x 25.4
1352x205x 25.4
1352x205x 25.4
Heat Exchanging Area
m
2
5.76
5.76
5.76
Performance
Air Flow Volume
m
3
/h
700/600/530
700/600/530
700/600/530
Sound Pressure Level
dB(A)
45/41/35
45/41/35
45/41/35
Dimension
Net Dim (W*D*H)
mm
570×570×260
570×570×260
570×570×260
Packing Dim (W*D*H)
mm
635x635x290
635x635x290
635x635x290
Net(Panel)
mm
650x650x55
650x650x55
650x650x55
Packing(Panel)
mm
710x710x80
710x710x80
710x710x80
Weight
Net(Body)
kg
18
18
18
Gross(Body)
kg
21
21
21
Net(Panel)
kg
3
3
3
Gross(Panel)
kg
5
5
5
Refrigerant Type
/
R410a
R410a
R410a
Pipe Dia
Liquid Side
mm(inch)
6.35(1/4)
6.35(1/4)
6.35(1/4)
Gas Side
mm(inch)
12.7(1/2)
12.7(1/2)
12.7(1/2)
Drainage
mm
20
20
20
Loading Qty
20/40/40H
unit
150/315/354
150/315/354
150/315/354
Note:
1. Cooling capacity test Condition:(27
℃
DB,19
℃
WB Indoor/35
℃
DB,24
℃
WB Outdoor);
Heating capacity test Condition:(20
℃
DB Indoor/7
℃
DB,6
℃
WB Outdoor);
connecting pipe length: 5M.
2. Datas may be changed withunit improvement. We keep the right to change the datas or specifications
withoutprior notice, please follow the datas listed on the nameplate.
Summary of Contents for AMCA-H09/4R1A
Page 1: ...AUX DC Inverter Free Match 50HZ R410A 1 SERVICE MANUAL DC Inverter Free Match R410a ...
Page 80: ...AUX DC Inverter Free Match 50HZ R410A Free Match outdoor unit 80 ...
Page 107: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 107 Outdoor protection phase sequence ...
Page 108: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 108 Cooling high pressure protection ...
Page 109: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 109 Heating high pressure protection ...
Page 110: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 110 Cooling low pressure protection ...
Page 111: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 111 Heating low pressure protection ...
Page 115: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 115 Sensor failure protection ...
Page 117: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 117 Poor effect ...
Page 118: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 118 ...
Page 119: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 119 Abnormal sound or viberation ...
Page 120: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 120 ...
Page 121: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 121 Abnormal odor ...
Page 123: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 123 Air conditioner water leakage ...
Page 132: ...AUX DC Inverter 1 Drive1 50HZ R410A Sensorresistance table 132 Wired controller XK 05 ...