AUX DC Inverter Free Match 50HZ R410A
Four-way cassette
17
6.5 Indoor unit suspension
◇
Select the suspension foundation:
The suspension foundation is a structure of either wooden frame or reinforced concrete. It must be
firm and reliable to bear at least 4 times weight of itself and capable of bearing vibration for long
periods.
◇
Fixing of suspension foundation:
◇
Fix the suspension bolts either as shown in the picture or by a steel or wooden bracket.
◇
If this unit is installed on a sloping ceiling, a cushion block should be installed between the ceiling and
the air outlet panel, in order to ensure that the unit is installed on a level surface.
This is as shown in the drawing as follows:
◇
Adjust the relative position of the suspension hook on the suspension bolt so that the unit can be in
level position in all directions. Check with a level gauge after installation to ensure that the indoor unit
is horizontal, otherwise it will cause water leakage, air leakage etc.
◇
Tighten the bolt and ensure that four hooks are in close contact with the nuts and washers,to fix the
indoor unitunder the ceiling.
◇
After the unit is installed ensure it is secure and does not shake or sway.
◇
Ensure that the centre of the indoor unit is in alignment with the centre of the opening in the ceiling.
Summary of Contents for AMCA-H09/4R1A
Page 1: ...AUX DC Inverter Free Match 50HZ R410A 1 SERVICE MANUAL DC Inverter Free Match R410a ...
Page 80: ...AUX DC Inverter Free Match 50HZ R410A Free Match outdoor unit 80 ...
Page 107: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 107 Outdoor protection phase sequence ...
Page 108: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 108 Cooling high pressure protection ...
Page 109: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 109 Heating high pressure protection ...
Page 110: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 110 Cooling low pressure protection ...
Page 111: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 111 Heating low pressure protection ...
Page 115: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 115 Sensor failure protection ...
Page 117: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 117 Poor effect ...
Page 118: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 118 ...
Page 119: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 119 Abnormal sound or viberation ...
Page 120: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 120 ...
Page 121: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 121 Abnormal odor ...
Page 123: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 123 Air conditioner water leakage ...
Page 132: ...AUX DC Inverter 1 Drive1 50HZ R410A Sensorresistance table 132 Wired controller XK 05 ...
Page 133: ...AUX DC Inverter 1 Drive1 50HZ R410A Sensorresistance table 133 ...