AUX DC Inverter Free Match 50HZ R410A
Installation
89
Equivalent pipe length conversion
Equivalent pipe length meansconverting pipe elbow to straight pipe length after considerate the pressure loss.
Elbow and Oil loop conversion tablet
Type
Pipe Dia.(mm)
Bend
Oil Loop
6.35
0.10
0.7
9.52
0.18
1.3
12.70
0.20
1.5
15.88
0.25
2.0
19.05
0.35
2.4
22.02
0.40
3.0
Equivalent pipe length L
=
ActualPipe length L+ Bend Qty× Equivalent pipe bend Oil Loop Qty× Equivalent
Oil Loop length
Sample:
AMCA-H09/4R1AActual Pipe length is 25 meters, Gas pipe diameter is 9.52
mm. If there’s 5 bends and 2 oil loops
during the installation, then the equivalent pipe length should be:
L=25+0.18×5+1.3×2=28.5(m)
◇
Specification of connection pipe for indoor unit and outdoor unit
Cooling Capacity(Btu/h)
18000
24000
27000
36000
42000
Connection Pipe (mm)
Liquid Pipe
Φ6.35
Gas Pipe
Φ9.52
Max. Length(Each)
15
Max. Height (m)
10
Max. Bend Qty
5
Extra R410a per meter when the pipe length is more
than 5 meter (kg)
0.022
Emptying or vacuum
Before charging the refrigerant to the system, to ensure that there is no impurities, water or non-condensable gas. So,
emptying and vacuum operation should be carried out.
◇
Vacuum: when process this operation please be sure that the connection pipe is tightened up.
1. Screw off the cover of maintenance valve connection, connect the pressure gauge to the connection of
maintenance valve
2. Connect the vacuum pump to the pressure gauge, turn on the vacuum pump and pressure gauge to process the
vacuum operation toward the indoor unit and piping, while to ensure that the absolute pressure is no less than
50Pa after this operation.
3. Turn off the pressure gauge and vacuum pump to keep the pressure in the same level in 20 minutes.
◇
Emptying: when process this operation, please disconnect the high pressure valve with liquid valve.
1. Connect the gas valve of the stop valve to the thimble side of the rubber hoses, the other side of rubber hoses
should be connected to the refrigerant tank.
2. Open the refrigerant tank valve, using the refrigerant inside the tank with high speed to empty the air in the indoor
unit and the connection piping. When the outlet air becomes mist (it feels cold by touching it), then the air is
emptied.
3. When ensure that the air is emptied, connect and tighten the high pressure valve of outdoor unit stop valve and
liquid side connection pipe, keep this state more than 10 seconds.
4. Use soapy what to test each connection junctions (including lengthen piping welding junction)
5. Confirmed that there is no leakage, turn off the valve of refrigerant tank, take down the rubber hose as well.
Summary of Contents for AMCA-H09/4R1A
Page 1: ...AUX DC Inverter Free Match 50HZ R410A 1 SERVICE MANUAL DC Inverter Free Match R410a ...
Page 80: ...AUX DC Inverter Free Match 50HZ R410A Free Match outdoor unit 80 ...
Page 107: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 107 Outdoor protection phase sequence ...
Page 108: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 108 Cooling high pressure protection ...
Page 109: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 109 Heating high pressure protection ...
Page 110: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 110 Cooling low pressure protection ...
Page 111: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 111 Heating low pressure protection ...
Page 115: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 115 Sensor failure protection ...
Page 117: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 117 Poor effect ...
Page 118: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 118 ...
Page 119: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 119 Abnormal sound or viberation ...
Page 120: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 120 ...
Page 121: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 121 Abnormal odor ...
Page 123: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 123 Air conditioner water leakage ...
Page 132: ...AUX DC Inverter 1 Drive1 50HZ R410A Sensorresistance table 132 Wired controller XK 05 ...
Page 133: ...AUX DC Inverter 1 Drive1 50HZ R410A Sensorresistance table 133 ...