AUX DC Inverter Free Match 50HZ R410A
Ceiling & Floor Type
25
3. Capacity amendment
3.1 Running range
Cooling capacity (Btu/h)
9000
12000
18000
Power supply
220-240V~/50Hz
Voltage
187~253V
Ambient temperature
Cooling
-10~52
℃
Heating
-15~24
℃
3.2 Amendment coefficient of cooling capacity under different indoor/outdoor
temperature(
K1)
Indoor
temperature(
℃)
Outdoor temperature(DB
)
DB
WB
25
30
35
40
45
50
22
15
0.97
0.92
0.87
0.96
0.77
0.75
24
17
1.03
0.98
0.94
0.89
0.84
0.80
27
19
1.10
1.05
1
0.95
0.90
0.86
29
21
1.16
1.11
1.06
1.02
0.96
0.91
32
23
1.22
1.17
1.13
1.08
1.02
0.98
Actual cooling capacity calculation:
Actual cooling capacity=amendment coefficient of cooling capacity × nominal cooling capacity
——nominal cooling capacity could be found from the performance parameters list
——amendment coefficient of cooling capacity could be found from table above.
3.3 Amendment coefficient of heating capacity under different indoor/outdoor
temperature K2
Outdoor temperature(
℃)
Indoor temperature(DB
)
DB
WB
15
20
25
-15
-16
0.64
0.59
0.55
-10
-12
0.71
0.66
0.62
-7
-8
0.76
0.72
0.67
-1
-2
0.79
0.74
0.70
2
1
0.81
0.76
0.72
7
6
1.04
1
0.96
10
9
1.10
1.06
1.01
15
12
1.16
1.12
1.07
Actualheatingcapacity calculation:
Actual heating capacity=amendment coefficient of heating capacity × nominal heating capacity
——nominal heating capacity could be found from the performance parameters list
——amendment coefficient of heating capacity could be found from table above.
Summary of Contents for AMCA-H09/4R1A
Page 1: ...AUX DC Inverter Free Match 50HZ R410A 1 SERVICE MANUAL DC Inverter Free Match R410a ...
Page 80: ...AUX DC Inverter Free Match 50HZ R410A Free Match outdoor unit 80 ...
Page 107: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 107 Outdoor protection phase sequence ...
Page 108: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 108 Cooling high pressure protection ...
Page 109: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 109 Heating high pressure protection ...
Page 110: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 110 Cooling low pressure protection ...
Page 111: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 111 Heating low pressure protection ...
Page 115: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 115 Sensor failure protection ...
Page 117: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 117 Poor effect ...
Page 118: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 118 ...
Page 119: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 119 Abnormal sound or viberation ...
Page 120: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 120 ...
Page 121: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 121 Abnormal odor ...
Page 123: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 123 Air conditioner water leakage ...
Page 132: ...AUX DC Inverter 1 Drive1 50HZ R410A Sensorresistance table 132 Wired controller XK 05 ...
Page 133: ...AUX DC Inverter 1 Drive1 50HZ R410A Sensorresistance table 133 ...