6.7 Drainage pipe
◇
Drainage pipes must be wrapped with heat insulation materials, otherwise it will cause frost or droplets, see picture
as follows:
Heat insulation material: rubber insulation pipe with the thickness of more than 8mm
◇
Drainage pipe must have a downward gradient (1 / 50 1 / 100) to avoid water backflow or leakage etc.
◇
When finish installation please carry out the drainage test to ensure that the water flow through the pipeline fluently,
and carefully observe the junction to ensure that there is no water leakage at the junction. If the unit is installed in
the newly built house, strongly recommend that this test taken before the CFiling installation. Even it is the heating
only unit, this test is unavoidable.
6.8 Remote controller receiver
◇
Installation site: recommend that the receiver is mounted with the distance of 30~50 cm to the indoor unit air
outlet(on your choice as well), while must ensure that the receiver can get the signal that the remote controller
sends, please refer to the following installation picture:
◇
Mounting hole set up: please use certain instrument to dig a square hole with 88*88mm on the ceiling
◇
Remote controller receiver installation.
Hold the two sides (with clip sides) of the receiver, set the spring clip in the vertical way then put it into
the mounting hole, if the two sides of the receiver is in the same level with the ceiling the installation is finished.
Summary of Contents for AMCA-H09/4R1A
Page 1: ...AUX DC Inverter Free Match 50HZ R410A 1 SERVICE MANUAL DC Inverter Free Match R410a ...
Page 80: ...AUX DC Inverter Free Match 50HZ R410A Free Match outdoor unit 80 ...
Page 107: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 107 Outdoor protection phase sequence ...
Page 108: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 108 Cooling high pressure protection ...
Page 109: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 109 Heating high pressure protection ...
Page 110: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 110 Cooling low pressure protection ...
Page 111: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 111 Heating low pressure protection ...
Page 115: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 115 Sensor failure protection ...
Page 117: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 117 Poor effect ...
Page 118: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 118 ...
Page 119: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 119 Abnormal sound or viberation ...
Page 120: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 120 ...
Page 121: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 121 Abnormal odor ...
Page 123: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 123 Air conditioner water leakage ...
Page 132: ...AUX DC Inverter 1 Drive1 50HZ R410A Sensorresistance table 132 Wired controller XK 05 ...
Page 133: ...AUX DC Inverter 1 Drive1 50HZ R410A Sensorresistance table 133 ...