Trouble shooting
104
6. Failure code display
When air condition has failure, the timing lamp on light board of indoor unit or the wired controller will
display different code according to different failure case.
No.
Default
INDICATOR/FLASH
(TIMES)
ERROR CODE ON
WIRE
CONTROLLER
COMMUNICATION
CODE
(SERIES)
1
Air Temp fault(Tao)
1
E1
11
2
Tcm or Tdef fault
2
E2
5
3
Tem fault
3
E3
12
4
Indoor Fan Motor fault
4
E4
13
5
I/O Communication fault
5
E5
7
6
Outdoor Fan Motor fault
10
F0
10
7
Comp Driver fault
11
F1
1
8
PFC fault
12
F2
2
9
Failure start of compressor
13
F3
3
10
Td fault
14
F4
4
11
Outdoor air temp sensor fault
16
F6
6
12
Over of less volt protection
17
F7
24
13
Com fault of main pcb&driver
18
F8
8
14
Outdoor EEPROM fault
19
F9
9
15
Refrigerant leak protection
20
J3/P3
15
16
Ts temp sensor fault
21
FA
16
17
Outdoor unit over current protection
22
J8/P8
18
18
Compressor high exhaust
temperature protection
23
J5/P5
19
19
High pressure protection failure
(cooling / heating)
24
J4/P4
20
20
Four way valve fault
25
H8
53
21
Drainage failure
26
H1
57
22
Remote control (manipulator)
communication fault
27
H2
58
23
Compressor exhaust temperature is
too low
28
H5
50
24
Low voltage switch fault
29
H6
51
25
Low pressure protection
30
H7
52
26
Evaporator inlet temperature sensor
fault (Te2)
31
H3
54
27
Evaporator outlet temperature
sensor fault (Te1)
32
H4
55
28
Inside and outside communication
line fault dislocation
33
H9
56
29
Anti-freezing protection in cooling
mode
/
/
21
Summary of Contents for AMCA-H09/4R1A
Page 1: ...AUX DC Inverter Free Match 50HZ R410A 1 SERVICE MANUAL DC Inverter Free Match R410a ...
Page 80: ...AUX DC Inverter Free Match 50HZ R410A Free Match outdoor unit 80 ...
Page 107: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 107 Outdoor protection phase sequence ...
Page 108: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 108 Cooling high pressure protection ...
Page 109: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 109 Heating high pressure protection ...
Page 110: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 110 Cooling low pressure protection ...
Page 111: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 111 Heating low pressure protection ...
Page 115: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 115 Sensor failure protection ...
Page 117: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 117 Poor effect ...
Page 118: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 118 ...
Page 119: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 119 Abnormal sound or viberation ...
Page 120: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 120 ...
Page 121: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 121 Abnormal odor ...
Page 123: ...AUX DC Inverter Free Match 50HZ R410A Trouble shooting 123 Air conditioner water leakage ...
Page 132: ...AUX DC Inverter 1 Drive1 50HZ R410A Sensorresistance table 132 Wired controller XK 05 ...
Page 133: ...AUX DC Inverter 1 Drive1 50HZ R410A Sensorresistance table 133 ...