Installation
For the input voltage at 208V
Nominal
Power
6kW
12kW
18kW
24kW
30kW
36kW
L1
Wire Size
2
6mm
2
16mm
2
16mm
2
25mm
2
25mm
2
25mm
Imax
0A
60A
60A
60A
125A
125A
L2
Wire Size
Imax
38A
38A
60A
103A
103A
125A
L3
Wire Size
Imax
38A
38A
60A
103A
103A
125A
Input
Breaker
63A
80A
100A
125A
125A
160A
2
6mm
2
16mm
2
16mm
2
25mm
2
25mm
2
25mm
2
6mm
2
16mm
2
16mm
2
25mm
2
25mm
2
25mm
Connection Steps:
The input connector board is located on the upper right side of the unit. Please ensure select
the suitable cables according to the table above.
1. Remove the input terminal protective cover from the rear panel of the DC power supply.
2. Scrap off the coating on the power cable tip, the bare portion is approx
mm.
15
3. Lessen the screw on the green connector.
4. Insert the input cables to the line and ground terminals respectively.
5. Using a suitably sized flat blade screwdriver tighten the screws on the top of terminal bock
assuring the wires are held tightly.
6. Replace the protective cover to avoid electric shock.
7. Sort out the input cables and fix them to the rear panel using a cable tie. The fixture is used
as strain relief. It is also used to prevent the AC plug from loosening and disconnecting due
to vibrations or similar.
8.5 Input Connection
!
Warning!
Connection to the AC input may only be carried out by qualified personnel!
Instruction not to position the equipment so that it is difficult to operate the disconnecting
device.
Note
For the input voltage at 400V
Nominal
Power
6kW
12kW
18kW
24kW
30kW
36kW
L1
Wire Size
2
2.5mm
2
4mm
2
6mm
2
10mm
2
10mm
2
16mm
Imax
0A
30A
30A
30A
63A
63A
L2
Wire Size
2
2.5mm
2
4mm
2
6mm
2
10mm
2
10mm
2
16mm
Imax
19A
19A
30A
49A
49A
63A
L3
Wire Size
2
2.5mm
2
4mm
2
6mm
2
10mm
2
10mm
2
16mm
Imax
19A
19A
30A
49A
49A
63A
Input
Breaker
32A
40A
40A
80A
80A
80A
It is suggested to use an external circuit breaker which protects, and can disconnect all
the current carrying conductors for the AC input cable.
Installation
71
PROFESSIONAL
INNOVATIVE BRANDING
SERVICE
70
PROFESSIONAL
INNOVATIVE BRANDING
SERVICE
The table below just gives the maximum output current for e ach phase. It is recommend that
keep the input cable as short as possible, because the longer the connection cable, the higher
the voltage loss due to the cable resistance.
Be sure to disconnect the AC mains before accessing the AC input.
The PE conductors is imperative and must always be wired! Otherwise an electric shock
hazard may exist.
Never touch cables or connectors directly after unplugging from mains supply as the danger
of electric shock remains.
Approved flexible cords with double insulation, suitable size, min. 60 deg C. Cable cross
section must be suitable for the maximum input current of the unit as in the following table.