Parallel/Series
6.4 Series Mode Connection Diagram
1 2
ON
1
4
3
2
System Bus Communication Cable
It doesn't matter which of the two master-slave connection sockets (RJ45) is connected to
the next unit.
Termination Resistor CAN-R
Flip dip switch 1 to ON (down) position.
Remote Sensing Wires
Use remote sensing in applications where load regulation at the load is critical. Use twisted
or shielded wires to minimize noise pick-up.
Output Connections
The DC terminal of every unit in the series operation is connected with correct polarity to
the next unit, using cables or copper bars with a proper withstand voltage and with short as
possible length.
!
Warning!
Besides being able to work as a power supply, the device is also an electronic load. Series
connection is not a permissible operating method for electronic loads and must not be
installed or operated under any circumstances!
1
2
3
4
Parallel/Series
6.3 Parallel Mode Connection Diagram
Load
-
+
1 2
ON
1
4
3
2
System Bus Communication Cable
It doesn't matter which of the two master-slave connection sockets (RJ45) is connected to
the next unit.
Termination Resistor CAN-R
Flip dip switch 1 to ON (down) position.
Remote Sensing Wires
Use remote sensing in applications where load regulation at the load is critical. Use twisted
or shielded wires to minimize noise pick-up.
Output Connections
The DC terminal of every unit in the parallel operation is connected with correct polarity to
the next unit, using cables or copper bars with a cross section according to the total system
current and with short as possible length.