109
017-882-B0-001 Rev. E (06/2018)
6.0 Specifications, Continued
International Models:
XM3-915M-HP
XM3-915P-HP
XM3-910E-HP
XM3-915E-HP
XM3-615CE-HP
XM3-622CE-HP
XM3-908HP
XM3-910HP
XM3-910M-HP
XM3-915HP
XM3-918HP
XM3-918D-HP
Parameters
Nominal AC Input
Voltage (VAC)
127
200-240
200-240
200-240
230
230
110-127
110-127
127
110-127
120
120/240
Nominal Input
Frequency (Hz)
60
60
50
50
50
50
60
60
60
60
60
60
Input Frequency
Tolerance (%)
±3
±3
±3
±3
±3
±3
±3
±3
±3
±3
±3
±3
Input Voltage
Operating Range
Tolerance (%)
-34 / +15
-30 / +20
-30 / +20
-30 / +20
-30 / +20
-30 / +20
-30 / +15 -30 / +15 -34 / +15
-30 / +15 -30 / +15
-20 / +15
Output Voltage (VAC)
63 / 89
63 / 89
48 / 63 / 89 63 / 89
48 / 63
63
63 / 89
63 / 89
63 / 89
63 / 89
63 / 89
63 / 89
Output Voltage
Regulation
-5 / +1
-5 / +1
-5 / +1
-5 / +1
-6 / +1.5
-6 / +1.5
-5 / +1
-5 / +1
-5 / +1
-5 / +1
-5 / +1
-5 / +2
Maximum Rated
Output Current
(Amps)
15
15
15 / 15 / 10 22 / 15
15
22
8
10
10
15
18
18
Maximum Output
Power (VA)
1350
1350
900
1350
900
1408
720
900
900
1350
1620
1620
Line Mode Efficiency
(%)
Up to 94
Standby Efficiency
(%)
Up to 91
Bulk Charger Current
(Amps @ 80% Load
& Nom line)
10
10
10
10
10
10
10
10
10
10
10
10
Battery Voltage
(VDC)
36
36
36
36
36
36*
36
36
36
36
36
36
Mechanical
Inverter Module
Front plug in, Hot swappable Inverter Module
Dimensions H x W x D
(in/mm)
7.8 x 15 (16.7 w/handle) x 10 (10.7 w/handle) / 198.1 x 381 (424.18 w/handle) x 254 (271.8 w/handle)
Weight (lb/kg)
60 / 27.2
60 / 27.2
53 / 24.1
67 / 30.5
53 / 24.1
67 / 30.5
48.5 / 22.0 49 / 22.3
49 / 22.3
60 / 27.2
60.5 / 27.5 69.4 31.5
Input Power
Connector
IEC 320/C20
Battery Connector
Anderson style 75A
Remote Temp Sensor
Ring lug fastens to negative terminal on center battery
Display
4 Line by 20 Character LCD with soft-key menu controls
LRI Connector
Anderson PP30
Mounting
Shelf mounts inside suitably rated electrical enclosure
Environment
Operating
Temperature (°C/°F)
-40° to +60°/ -40° to +140° (derate by 2° to 3.6° per 1000 feet above 3000 feet)
Storage Temperature
(°C/°F)
-40° to +70°/ -40°to +158°
Humidity (%)
0–95 non-condensing (relative)
Conformal Coating
All Printed Circuit Board assemblies to prevent moisture related failure
Safety Compliance
UL/CSA 60950-1,
UL 1778, CSA 107.3
(NRTL/C)
Y
Y
Y
Y
Y
Y
Y
Y
IEC 60950-1 (CB)
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
IEC/EN 62040-1
Y
Y
Safety Mark
NRTL/C
NRTL/C
CE
CE
NRTL/C
BSMI
(optional)
NRTL/C
NRTL/C
NRTL/C
BSMI
(optional)
NRTL/C
NRTL/C
EMC Compliance
FCC Part 15 Class A,
ICES 003
Y
Y
Y
Y
Y
Y
Y
Y
IEC/EN 50083-2
(CATV)
Y
Y
IEC/EN 62040-2 (UPS)
Y
Y
Y
Y
CISPR22
Y
Y
Y
Y
6.2 Specifications (Alpha XM3-HP CableUPS International Models)
Table A-2, International Specifications