57
017-882-B0-001 Rev. E (06/2018)
2.0 Installation, Continued
Fig. 2-35, Select Language in PWR CNFG Menu
Two output connectors will be present on the side of the front panel whether or not the optional AlphaDOC is
installed. If an AlphaDOC is not installed, the output voltage (Output 1) will be present on both connectors as the
connectors are wired in parallel by means of an internal split ("Y") wiring harness. If an optional AlphaDOC is
installed, the split wiring harness is replaced with individiual wiring for Output 1 and Output 2 (
Secondary loads to
be connected to Output 2)
.
NOTICE
:
The default language is set to English. Unless the XM3 is ordered preset to another language, the language can
be changed through the PWR CNFG (Power Configuration) menu. Pressing the PWR (Power) softkey while in the
OPERATION NORMAL
screen opens the Power Info Menu display (the first letter of the top line will blink indicating
it is the active line; shown in orange). Pressing ENTR from this screen opens the
PWR CNFG Menu. Scroll down to
the SELECT LANGUAGE menu to set to the desired language, see Figure 2-35.
NOTICE
:
Power Config Menu
Default
Range
PWR CNFG <ENTR>
Power Config Menu
Default
Range
SELECT LANGUAGE
English
Spanish
French
Portuguese
German
P
WR CNFG <ENTR>
OUTPUT VOLTS
OUTPUT CURR
ENTR
ESC
21. Once the unit is running on line voltage, perform a Self Test by pressing and holding the test button for 1-2
seconds with a pen (or similar object). Wait for Self Test completion before proceeding (see
Section 3.1.1, Self
Test Operation
).
22. Perform standby test by shutting off utility breaker and verifying unit goes into standby and supports the load.
23. Re-apply AC power and verify unit goes to Line Mode.
If the unit is operating from batteries, the Self Test will not initiate. Check input breaker and input line cord.