80
017-882-B0-001 Rev. E (06/2018)
3.0 Operation, Continued
Event Logging App:
The APP card can log 768 events. This log does roll-over when the maximum size has been reached. When the roll-over
occurs, the oldest 64 records are erased to make room for new records. Once a roll-over has occurred, the number of
records available will be between 704 and 768. See Table 3-3 for a list of Events and Alarms that are logged.
This is an example event log screen shot. The
“EL” denotes the event log, and the record was
time stamped on February 6, 2012 at 8:38:33 in
the morning.
The up and down arrow keys step through the
log records forward and backward in time.
TABLE OF EVENTS/ALARMS LOGGED
ALPHADOC OPTION
DNSTRM POWER FAULT
OUTPUT 2 TRIPPED
APP CARD CODE DOWNLOADED
HIGH BATT VOLTS
OUTPUT FAILURE
APP CARD HARDWARE STATUS
HIGH BATTERY ALARM
OUTPUT OVERLOAD
APP CARD REAL TIME CLOCK SET
HW COMPATIBILITY
OUTPUT OVERLOAD ALARM
APP CARD RESET CAUSE
INPUT FAILURE
PDB EEPROM ERROR
APP CARD TECHNICIAN CODE ENTERED
INPUT FAILURE ALARM
POWER SUPPLY INPUT CURRENT LIMIT ALARM
APP OPTION
INPUT OVER CURR
REFRESH
BATT TEMP PROBE
INV EEPROM ERROR
SAG COMPATIBILITY
BATTERY EOD
INVERTER ALARM
SAG DELTA MEAN
BATTERY FAIL
INVERTER ENABLE
SAG NO HARNESS
BATTERY LOG CLEARED
INVERTER TEMP
SAG NOT CALIBRATED
BATT. TEMPERATURE PROBE STATUS ALARM
LINE ISOLATION
SAG OPTION
CHARGER ENABLE
LINE ISOLATION ALARM
SAG RELAY STUCK
CHARGER FAIL ALARM
LOW BATT VOLTS
SELF TEST ALARM
CHARGER FAILURE
LOW BATTERY SHUTDOWN ALARM
SELF TEST FAIL
CLOCK NOT SET
MAJOR APPLICATION ALARM
SELF TEST FAIL ALARM
CM IP ADDRESS
MINOR APPLICATION ALARM
STR X MISWIRED
CM MAC ADDRESS
NO BATTERIES
SURGE MOV FAIL
CONFIG ERROR
OUTPUT 1 ENABLE
TM COMPATIBILITY
CONFIGURATION LOG CLEARED
OUTPUT 1 TRIPPED ALARM
X BAL STAGE
CPE IP ADDRESS
OUTPUT 1 TRIPPED
CPE MAC ADDRESS
OUTPUT 2 ENABLE
Table 3-4, Logged Events and Alarms
EL 02/06/12
08:38:33.00
MINOR ALARM: XM3-1
INPUT FAILURE=ALARM
ESC