017-882-B0-001 Rev. E (06/2018)
2.0 Installation, Continued
Fig. 2-11, Battery Sense Wiring, 36V, 2 Battery Configuration
Fig. 2-12, Battery Sense Wiring, 36V, 4 Battery Configuration
+
+
+
+
-
-
-
-
1
2
3
4
5
6
7
8
+
+
-
-
black
(–)
red
(+)
black
(–)
red
(+)
1
2
3
4
5
6
7
8
AlphaCell 18v4 Battery sense wiring as part of a new installation.
B1
B2
A1
A2
A1
Vbatt B2 [D] 36V
Vbatt
A2 [C] 36V
Vbatt
A1 [C] 18V
String (–)
Vbatt B1 [D] 18V
A/B (C/D) NEG
A2
String (–)
A/B NEG
Vbatt
A1 [C] 18V
Vbatt
A2 [C] 36V
DM3X A/B, C/D
Connector
DM3X A/B, C/D
Connector
to
power
supply
to
power
supply
Battery Voltage Sense Cable, 2 Battery string
(Alpha p/n, 874-842-40)
Battery Voltage Sense Cable, 4 Battery string
(Alpha p/n, 874-842-41)
Each AlphaCell XTV 18V4 is shipped with a jump
-
er cable to be used in dual string configurations.
NOTICE
:
String (–)
The AlphaCell XTV 18V4 does not support
the Smart AlphaGuard (SAG) battery charge
management function. The SAG functionality
will be disabled in XM3 Power supplies
configured with Platform 14 firmware code.
To avoid possible alarms, the SAG should be
disconnected and the sense harness replaced
with a standard DSM harness connected to the
Battery A/B, C/D connector on the DM3X If the
SAG is still installed, selecting the 18V battery
will result in a SAG Compatibility alarm.
NOTICE
: