3.0 Operation, Continued
Percent Load:
The percentage of the output current versus the rated output current.
Power Supply Priority Level:
The operator may select the power supply priority level in context of its deployed location in the
cable network. This setting is a reference for the customers only and does not affect the power supply performance. The settings
are Normal (default), High, or Critical.
PowerStave Mode:
A mode of the SAG initiated by a "turn off" command from the power supply. In this mode the software disables
the balancer including all relays, and it turns off all the LEDs. It only detects voltages on a query from the power supply.
REFRESH Enable:
This enables a 24-hour REFRESH charge of the batteries. This is recommended for batteries that have been
in storage.
Reset Standby:
This resets the Standby Total and Standby Events.
REST Enable:
Enables the REST battery charger mode. The value is read-only when Alphacell battery models are selected, and
is programmable when the battery model is Other.
RMODE:
An inverter control that limits the peak output voltage. When R-Mode is enabled the XM3 will reduce the inverter mode
output peak voltage for powering legacy HFC equipment with lower peak input voltage tolerances. For 90VAC output RMODE,
the XM3 inverter firmware version must be 1.09.0 or higher. For 60VAC output RMODE, a minimum inverter firmware version of
1.12.0 or higher is required.
SAG FW Vx.xx.x:
The Smart AlphaGuard firmware version that is installed. This is hidden if the SAG is not installed.
SAG Option:
Indication whether the Smart AlphaGuard is installed. This is automatically sensed.
SAG ################:
The Smart AlphaGuard Serial Number. This is hidden if the SAG is not installed.
Self Test:
When programmed to YES, the power supply automatically starts a Self Test. If the power supply is used in a non-standby
application, the Battery Capacity variable must be programmed to “0” to disable the battery maintenance cycle portion of a Self Test.
Set Defaults:
When programmed to YES, the programmable data levels (with the exception of Last Standby Time, Total Standby
Time, Standby Events, Device Address, Total Run Time, Battery Type and Language) are reset to the original factory settings.
Set Language:
The display text language can be set to English, Spanish, French, German, or Portuguese.
Standby Events:
A standby events counter. This does not include Self Test events. Resetting factory defaults does not clear
Standby Events
or
Standby Total
.
Standby Total:
The total amount of time the power supply has operated in standby mode. This does not include Self Test time and
represents the sum total number of minutes of AC line failure since the last time the counter was reset. Resetting factory defaults
does not clear
Standby Events
or
Standby Total
.
System Contact:
The textual identification of the contact person for the managed power supply, together with information on how
to contact this person. This item can be entered via the transponder Web page or status monitoring firmware.
System Location:
The physical location of the power supply. This item can be entered via the transponder Web page or status
monitoring firmware.
System Name:
An administratively assigned name for the managed power supply. This item can be entered via the transponder
Web page or status monitoring system.
Test Countdown:
The number of days remaining before the next scheduled automatic Self Test initiates. This variable is
programmable and you can select the day the autotest sequence will begin. This counter has no effect if test interval is set to 0.
Test Duration:
Automatic Self Test duration timer. This sets the number of minutes of a battery maintenance cycle test. This timer
applies to automatically or manually initiated tests.
Test Inhibit:
Becomes active when programmed by the operator (or when the unit runs in inverter mode for more than 5 minutes).
The power supply delays the start of a scheduled Self Test for seven days if the test countdown is less than seven days (See
Section 3.7, Automatic Performance Test
for complete details).
Test Interval:
Automatic Self Test control timer. The number of days between battery maintenance cycle tests. Set this value to
zero to disable automatic Self Test.
TM ################:
The serial number of the XM3 transformer module.
Total Run Time:
The amount of time (in days) the power supply has functioned in any mode of operation. This is not a resetable
value.
XM3 FW Vx.xx.x:
The firmware version of the XM3 micro board.