017-882-B0-001 Rev. E (06/2018)
1.0 Introduction, Continued
Programmable parameters (with AlphaDOC installed) are:
Channel 1 Overcurrent Limit:
The RMS current level that causes the Output 1 protection relay to trip after a specified
delay (overcurrent tolerance period).
Channel 2 Overcurrent Limit:
The RMS current level that causes the Output 2 protection relay to trip after a specified
delay (overcurrent tolerance period).
Retry Delay:
The time between each attempt to restart an output in the event of an overcurrent event.
Retry Limit:
The number of times the power supply attempts to restart an output connection. Once the RETRY LIMIT
is exceeded, standard models attempt to restart the output connection every 30 minutes. Set this parameter to “zero” to
disable the “automatic retry” function.
Overcurrent Tolerance Period (20-9900ms):
In the event of an overcurrent episode, the amount of time an output
overcurrent condition is permitted on either output connection. Once this time expires, the output protection relay disables
its output feeder.
Output 1 Reset/Output 2 Reset:
This manually resets corresponding tripped output. These are not displayed if the
corresponding output is not tripped.
Read Only AlphaDOC Menu Items:
AlphaDOC Option: Automatically senses and indicates whether the AlphaDOC is installed.
AlphaDOC FW: Firmware version installed in the AlphaDOC.
DOC ##########: Serial number of the AlphaDOC.
Programming the AlphaDOC
Fig. 1-11, 5-Position Output Voltage Terminal Block
For XM3-910E-HP and XM3-615CE-HP models, a 5-position terminal block is included, see Fig. 1-11.
NOTICE
:
Programming any of the above parameters will reset the “trip/retry” counters.
NOTICE
:
If the optional AlphaDOC is not installed, the values shown under the “AlphaDOC OPTION” line of the Smart
Display are hidden.
NOTICE
:
63V 89V
48V