70
017-882-B0-001 Rev. E (06/2018)
3.0 Operation, Continued
3.3.1 Power Information and Configuration
Pressing the PWR (Power) softkey while in the
OPERATION NORMAL screen opens the Power Info Menu display (the
first letter of the top line will blink indicating it is the active line; shown in orange). Pressing ENTR from this screen opens
the PWR CNFG Menu. Cycling through each menu item and following the prompts on the lower line will enable the user to
configure the parameters shown in the menu.
Power Config Menu
Default
Range
SELF TEST
OFF
ON / OFF
TEST INTERVAL
30 DAYS
0 –365 DAYS
TEST DURATION
10 MIN
5–180 MINUTES
TEST COUNTDOWN
30 DAYS
0–365 DAYS
TEST INHIBIT
+7 Days=Test Inhibit;
0=OFF
DISCHARGE LVL
TIMED
TIMED, 10–50%
FREQ RANGE
3.0HZ
1–6HZ
ALPHADOC OPTION
AUTO
NO / YES
ALPHADOC FW
VX.XX.X
DOC #####
OUTPUT 1 RESET
ON
NO
1
OUTPUT 2 RESET
ON
NO
1
CURR LIMIT 1
110% RATING
3.0–25.0A
2
CURR LIMIT 2
110% RATING
3.0–25.0A
2
RETRY DELAY
60S
5–301S
2
RETRY LIMIT
20
0–40
2
OVER CURR TOL
3000MS
20–9900
MS
2
OUTPUT VOLT REG
3
FINE/COARSE
RMODE
DISABLE
ENABLE/DISABLE
PS PRIORITY
NORMAL
INPUT LIMIT
INP V SETTING
4
120V/240V
SET DEFAULTS
NO
NO / YES
RESET STANDBY
NO
NO / YES
DEVICE ADDRESS
1
0–5
SELECT LANGUAGE
English
Spanish, French,
Portuguese, German
Hidden if no
AlphaDOC is
installed
* Displayed only if AlphaDOC with N+1 option is installed
1
Output 1 & 2 Reset will be hidden if the corresponding output is not tripped.
2
Ablity to select available if Optional AlphaDOC installed
3
Hidden for XM3-918D-HP models
4
Displayed only for XM3-918D-HP models
P
WR CNFG <ENTR>
OUTPUT VOLTS
OUTPUT CURR
ENTR
ESC
POWER INFO MENU
PWR CNFG <ENTR>
OUTPUT VOLTS
48,63 or 89 VAC
0
–
101 VAC
OUTPUT CURR
10.5A
0–40 A
OUTPUT 1 CURR
1
6.8A
OUTPUT 2 CURR
1
8.0A
N+1 VALID
2
YES/NO
OUTPUT POWER
2000W
PERCENT LOAD
80%
0–255%
INPUT VOLTS
120V
0–325 VAC
INPUT CURRENT
(4.5A)
0–25 A
INPUT FREQ
60HZ
42HZ–67.5HZ
INPUT POWER
2000W
OPER MODE
LINE/STANDBY
STANDBY EVENTS
0–65535 EVENTS
CURRENT OUTAGE
0–65535 MIN
LAST OUTAGE
0–65535 MIN
LAST EVENT
(DD:HH:MM)
TOTAL RUN TIME
0–65535 DAYS
STANDBY TOTAL
0–65535 MIN
LAST STBY RESET
0–65535 DAYS
XM3 FW V1.11.0
V
x
,
xx
,
x
TM #######
IM ########
BATT INFO
<ENTR>