Chapter 5
Module Configuration Attributes
484
Rockwell Automation Publication MOTION-RM003I-EN-P - February 2018
The purpose of Demo Mode is to allow demonstration of products in
non-industrial environments. It is not intended for use in real motion
applications.
Converter Overtemperature User Limit
Usage
Access
T Data Type
Default
Min
Max
Semantics of Values
Optional - BD
Set
REAL
0
0
Degrees Celsius (°C)
This attribute sets the user limit for the Converter Overtemperature UL
exception.
Converter Thermal Overload User Limit
Usage
Access
T Data Type
Default
Min
Max
Semantics of Values
Optional - BD
Set
REAL
100
0
% Converter Rated
This attribute sets the user limit for the Converter Thermal Overload UL
exception.
Converter Ground Current User Limit
Usage
Access
T Data Type
Default
Min
Max
Semantics of Values
Optional - BD
Set
REAL
100
0
% Factory Limit
This attribute sets the user limit for the Converter Ground Current UL
exception.
Bus Regulator Overtemperature User Limit
Usage
Access
T Data Type
Default
Min
Max
Semantics of Values
Optional - BD
Set
REAL
0
0
Degrees Celsius (°C)
This attribute sets the user limit for the Bus Regulator Overtemperature UL
exception.