CIP Axis Attributes
Chapter 4
Rockwell Automation Publication MOTION-RM003I-EN-P - February 2018
267
Hookup Test Feedback Channel
Usage
Access
T Data
Type
Default
Min
Max
Semantics of Values
Required - E
Set/
SSV*
USINT
1
1
2
Feedback Channel
1 = Feedback 1
2 = Feedback 2
*
Indicates the attribute cannot be set while the drive power structure is enabled (Power Structure Enable bit in CIP Axis Status
is true).
The Test Feedback Channel attribute is used by the Hookup Test service when
the 'Feedback' test is selected to determine which feedback channel to test.
See also
Inertia Test Status Attributes
Inertia Test Configuration Attributes
Auto-Tune Configuration Attributes
These are the attributes that are associated with hookup result status applied to a
Motion Control Axis
Hookup Test Status
Usage
Access
T Data
Type
Default
Min
Max
Semantics of Values
Required - All
Get/GSV
USINT
-
-
-
Enumeration
0 = Test Process Successful
1 = Test in Progress
2 = Test Process Aborted
3 = Test Process Timed-out
4 = Test Process Faulted
5 = Test Failed - no feedback 1
counts
6 = Test Failed - no feedback 2
counts
7...255 = Reserved
The Hookup Test Status attribute returns status of the last Run Hookup Test
service on the targeted drive axis. The Hookup Test Status attribute can be used to
determine when the hookup test service has successfully completed. Conditions
may occur, however, that make it impossible for the drive to properly perform the
Hookup Test Result Attributes