214 2CDC508134D0202 | FCA/S 1.x.x.1
No.
Functionality
communication object name
Data type
Flags
14
Status Valve purge
Output A
Output A/B
1 bit
DPT 1.003
C, R, T
This communication object is enabled with the option
Yes
via the parameters
Enable valve purge
and the communication
object
Status Valve purge
1 bit in
p. 113. The valve purge status is indicated via this
communication object.
The status is sent if:
a request is received via the communication object
Request status values
and the parameter is set to
After request
or
After a change or request
.
the value of the communication object has changed and the parameter is set to
After request
or
After a change or
request
.
a read request is carried out on this communication object.
Telegram value:
0 = Valve purge inactive
1 = Valve purge active
Note
The status is displayed as soon as a valve purge has been activated. The status remains active, even when
the valve purge has been interrupted, e.g. by a priority.
15
Priority 1, Forced operation
Output A
Output A/B
1 bit
DPT 1.001
C, W
This communication object is enabled if the parameter
Safety priority 1
has been selected with the option
Forced operation
(1-bit object) in
If a telegram with the value 1 or 0 is received (can be parameterized), the output is forcibly operated and the operation is
blocked.
The reaction of the output with an active forced operation is set in parameter
Control value on forced operation in % [0…100].
Telegram value:
1/0 = Forced operation
15
Priority 1, Block
Output A
Output A/B
1 bit
DPT 1.001
C, W
This communication object is enabled if the parameter
Safety priority 1
has been selected with the option
Block
If a telegram with the value 1 or 0 is received (can be parameterized), the output remains in its current position and the
operation is blocked.
Telegram value:
1/0 = Block
16
Priority 2, Forced operation
Priority 2, Block
Output A
Output A/B
Output A
Output A/B
1 bit
DPT 1.001
1 bit
DPT 1.001
C, W
See communication object 15
17
Priority 3, Forced operation
Priority 3, Block
Output A
Output A/B
Output A
Output A/B
1 bit
DPT 1.001
1 bit
DPT 1.001
C, W
See communication object 15