ABB i-bus
®
KNX
Commissioning
FCA/S 1.x.x.1 | 2CDC508134D0202 113
3.2.3.5
Parameter window Function
In this parameter window, various functions for each output can be activated. The functions are identical
for the operation modes
Valve drive, thermoelectric (PWM)
,
Valve drive, motor-driven (3-point)
and
Valve
drive, analog (0...10 V)
.
Enable function "Priority and safety
operation"
Options:
No
Yes
Yes:
p. 117, is enabled.
Enable communication object
"Status Control value" 1-bit/byte
Options:
No
Yes
This parameter enables the communication object
Status Control value
. The control status of the output is
sent via this communication object.
Yes:
The communication object
p. 212, is enabled.
Dependent parameters: