ABB i-bus
®
KNX
Device technology
FCA/S 1.x.x.1 | 2CDC508134D0202 61
2.6
Manual operation
Function of manual operation
Manual operation facilitates on-site operation of the device. Manual operation is enabled as standard and
can be switched on and off using the
Manual operation
button .
Switching on manual operation:
Press the button until the yellow LED lights continuously.
Switching off manual operation:
Press the button briefly. The yellow LED continues to flash for 2 seconds.
After connection to the KNX, an ETS download or ETS reset, the device is in
KNX operation
. The LED
is off. All LEDs indicate the current state.
Note
If
Manual operation
is generally disabled or is disabled via communication object
Block manual
operation
, the LED flashes during the button push.
A switchover from
KNX operation
to the
Manual operation
mode does not occur.
Note
If manual operation is activated, the current fan speed remains set and can only be operated manually.
Here any limitations, forced operations and programmed dwell times are not considered.
If manual operation is deactivated, the fan sets to a speed to which it would also be set without manual
operation, e.g. via the value of the communication objects. The setting occurs with the parameterized
dwell times.