Commissioning
FCA/S 1.x.x.1 | 2CDC508134D0202 213
No.
Functionality
communication object name
Data type
Flags
12
Fault control value
Output A
Output A/B
1 bit
DPT 1.005
C, R, T
This communication object is enabled if the parameter
Monitoring control values e.g. thermostat
has been selected with the
option
Yes
in
Output (Valve drive, thermoelectric (PWM))
This communication object indicates a possible fault in conjunction with the room thermostat. The communication object
Control value, heating, ON/OFF
or
Control value, heating, continuous (PWM)
can be monitored cyclically. If the control value
from the sending room thermostat remains missing for a parameterizable time, a telegram with the value 1 is sent.
The communication object value is sent via the communication object
Request status values
depending on the
parameterization, on a change and/or request.
Telegram value:
0 = No fault
1 = Fault
13
Activate purge
Output A
Output A/B
1 bit
DPT 1.003
C, W
This communication object is enabled with the option
Yes
via the parameter
Enable valve purge
in
p. 113. 'The valve purge is enabled via this communication object.
Telegram value:
0 = End valve purge, valve will be closed
1 = Start valve purge, valve will be opened
The purging cycle time is restarted if automatic valve purge has been activated at start-up of the device.
The purging cycle time will be restarted at the end of the actual purging period. The parameterized valve purging duration is
included here.
If a valve purge currently underway is interrupted by a manual valve purge or a control value, which reached the
parameterized purge value, the purge cycle time is restarted. If the active purge duration was less that the parameterized
purge duration, this will not be taken into consideration. In this case, the actual purge cycle time is shorter in duration by the
active purge duration.
Note
A valve purge not undertaken due to a higher priority will no longer be undertaken.
The following functions are executed with telegram value 0.
A valve purge currently under way is interrupted.
The purge cycle with automatic valve purging will be restarted.