Commissioning
FCA/S 1.x.x.1 | 2CDC508134D0202 233
3.3.5.2
Communication objects Value/forced operation
No.
Functionality
communication object name
Data type
Flags
90
Block
Input a:
Value/forced operation
1 bit
DPT 1.003
C, W
This communication object is enabled if the parameter
Input a
has been selected with the option
Value/forced operation
in
, p. 170, and the parameter
Enable communication object "Block" 1-bit
has then been
selected with the option
Yes
in
Using the communication object
Block
, the input can be blocked or enabled. With activated communication object
Block
the
inputs are blocked.
Note
When the input is blocked there is fundamentally no reaction to a signal change, but:
Waiting for a long button operation or a minimum signal duration is suspended.
The parameter setting
8-bit scene
ends saving.
communication objects continue to be updated and sent if necessary.
When enabling an input, a change of the signal states (as opposed to before the block) leads to immediate
processing, e.g.:
The minimum actuation or detection of a long/short button push starts.
communication objects send their current value if necessary.
Telegram value:
0 = Enable input a
1 = Block input a
91
Value 1
Input a:
Value/forced operation
DPT variable
C, T
This communication object is enabled if the parameter
Input a
has been selected with the option
Value/forced operation
in
This communication object sends a value on the bus with short operation when opening or closing the contact. The value and
data type can be freely set in the parameters.
1 bit value [0/1]
2 bit value [0…3]
1-byte value [-128...127]
1-byte value [0...255]
1-byte value (8-bit scene)
2-byte value [-32,768...32,767]
EIS 1
EIS 8
EIS 14
EIS 6
EIS 6
EIS 10
DPT 1.001 switch telegram
DPT 2.001 forced operation
DPT 6.010 value
DPT 5.010 value
DPT 18.001 control scene
DPT 8.001 value
2-byte value [0...65,535]
2 byte value [EIB floating point]
3 byte value [time, weekday]
4-byte value [0...4294967295]
EIS 10
EIS 5
EIS 3
EIS 11
DPT 7.001 value
DPT 9.001 temperature
DPT 10.001 time, weekday
DPT 12.001 value
4-byte value [-2147483648...2147483647]
EIS 11
DPT 13.001 value
92
Value 2
See communication object 91
93…99
Not assigned
100…119
Input b, c